LG C Series User Manual

Page 4

Advertising
background image

(2) Wiring

…

Do not connect a power factor correction capacitor, surge suppressor, or RFI filter to the output of
the inverter.

…

The connection orientation of the output cables U, V, W to the motor will affect the direction of
rotation of the motor.

…

Incorrect terminal wiring could result in the equipment damage.

…

Reversing the polarity (+/-) of the terminals could damage the inverter.

…

Only authorized personnel familiar with Cerus inverter should perform wiring and inspections.

…

Always install the inverter before wiring. Otherwise, you may get an electric shock or have bodily
injury.

(3) Test run

…

Check all parameters prior to operation. Changing parameter values might be required depending
on the load.

…

Always apply permissible range of voltage to the each terminal as indicated in this manual.
Otherwise, it could lead to inverter damage.

(4) Operation precautions

…

When the Auto restart function is selected, stay away from the equipment as a motor will restart
suddenly after a fault stop.

…

The Stop key on the keypad is valid only when the appropriate function setting has been made.
Prepare an emergency stop switch separately.

…

If a fault reset is made with the reference signal present, a sudden start will occur. Check that the
reference signal is turned off in advance. Otherwise an accident could occur.

…

Do not modify or alter anything inside the inverter.

…

Motor might not be protected by electronic thermal function of inverter.

…

Do not use a magnetic contactor on the inverter input for frequent starting/stopping of the inverter.

…

Use a noise filter to reduce the effect of electromagnetic interference. Otherwise nearby electronic
equipment may be affected.

…

In case of input voltage unbalance, install AC reactor. Power Factor capacitors and generators may
become overheated and damaged due to potential high frequency noise transmitted from inverter.

…

Before operating unit and prior to user programming, reset user parameters to default settings.

…

Inverter can easily be set to high-speed operations. Verify capability of motor or machinery prior to
operating unit.

…

Stopping torque is not produced when using the DC-Brake function. Install separate equipment
when stopping torque is needed.

(5) Fault prevention precautions

…

Provide a safety backup such as an emergency brake, which will prevent the machine and
equipment from hazardous conditions if the inverter fails.

(6) Maintenance, inspection and parts replacement

…

Do not conduct a megger (insulation resistance) test on the inverter.

…

Refer to Chapter 13 for periodic inspection (parts replacement).

(7) Disposal

…

Handle the inverter as an industrial waste when disposing of it.

(8) General instructions

…

Many of the diagrams and drawings in this instruction manual show the inverter without a circuit
breaker, a cover or partially open for instructional purpose only. Please place the cover with circuit
breakers and follow this instruction manual when operating the inverter for the safety.