Chapter 6. Basic operation

Frequency setting via potentiometer & operating via the Run key

1

-. Apply AC input power to the inverter.

2

-. When 0.0 is displayed, press the Up (

S) key three times.

3

-. drv is displayed. Operating method is selectable.
-. Press the Prog/Ent (

z) key.

4

-. Check the present operating method (“1” is run via control terminal)
-. Press the Prog/Ent (

z) key and then Down (T) key once.

5

-. After setting “0”, press the Prog/Ent (

z) key.

6

-. “drv” is displayed after “0” is blinking. Operation method is set via the Run key on the
keypad.
-. Press the Up (

S) key once.

7

-. Different frequency setting method is selectable in this code.
-. Press the Prog/Ent (

z) key.

8

-. Check the present frequency setting method (“0” is run via keypad).
-. Press the Up (

S) key twice.

9

-. After checking “2” (frequency setting via potentiometer), press the Prog/Ent (

z) key.

10

-. “Frq” is displayed after “2” is blinking. Frequency setting is set via the potentiometer on
the keypad.
-. Turn the potentiometer to set to 10.0 Hz in either Max or Min direction.

11

-. Press the Run key on the keypad.
-. FWD lamp begins to blink and accelerating frequency is displayed on the LED.
-. When run frequency 10Hz is reached, 10.0 is displayed as shown left.
-. Press the STOP/RST key.

12

-. FWD lamp begins to blink and decelerating frequency is displayed on the LED.
-. When run frequency is reached to 0Hz, FWD lamp is turned off and 10.0 is displayed as
shown left.

220VAC

L1(R)

L2(S)

P

P1

N

G

U

V

W

Motor

MIN

MAX

RUN

STOP/RST

Freq.

Run key

10 Hz

STOP/RST key

Wiring Operating

pattern