Chapter 7. Function list

Function group 1

LED

display

Parameter

name

Min/Max

range

Description

Factory

defaults

Adjustable

during run

Page

F24 [Frequency

high/low limit
select]

0/1

ƒ

This parameter sets high and low limit of

run frequency.

0 X

9-19

F25
2)

[Frequency
high limit]

0/400
[Hz]

ƒ

This parameter sets high limit of the run

frequency.

ƒ

It cannot be set above F21 – [Max

frequency].

60.0 X

F26 [Frequency

low

limit]

0/400
[Hz]

ƒ

This parameter sets low limit of the run

frequency.

ƒ

It cannot be set above F25 - [Frequency

high limit] and below F23 – [Start frequency].

0.5 X

9-19

0 Manual

torque

boost

F27 [Torque

Boost

select]

0/1

1

Auto torque boost

0 X

9-17

F28 [Torque

boost

in forward
direction]

0/15 [%]

ƒ

This parameter sets the amount of torque

boost applied to a motor during forward run.

ƒ

It is set in percent of Max output voltage.

5 X

9-17

F29 [Torque

boost

in reverse
direction]

ƒ

This parameter sets the amount of torque

boost applied to a motor during reverse run.

ƒ

It is set as a percent of Max output

voltage

5 X

9-17

0 {Linear}

9-15

1 {Square}

9-15

F30 [V/F

pattern]

0/2

2 {User

V/F}

0 X

9-16

F31
3)

[User V/F
frequency 1]

0/400
[Hz]

15.0 X

F32 [User

V/F

voltage 1]

0/100 [%]

25

X

F33 [User

V/F

frequency 2]

0/400
[Hz]

30.0 X

F34 [User

V/F

voltage 2]

0/100 [%]

50

X

F35 [User

V/F

frequency 3]

0/400
[Hz]

45.0 X

F36 [User

V/F

voltage 3]

0/100 [%]

75

X

F37 [User

V/F

frequency 4]

0/400
[Hz]

60.0 X

F38 [User

V/F

voltage 4]

0/100 [%]

ƒ

This parameter is active when F30 – [V/F

pattern] is set to 2 {User V/F}.

ƒ

It cannot be set above F21 – [Max

frequency].

ƒ

The value of voltage is set in percent of

H70 – [Motor rated voltage].

ƒ

The values of the lower-numbered

parameters cannot be set above those of
higher-numbered.

100 X

9-16

F39 [Output

voltage

adjustment]

40/110
[%]

ƒ

This parameter adjusts the amount of

output voltage.

ƒ

The set value is the percentage of input

voltage.

100 X

9-16

F40 [Energy-saving

level]

0/30 [%]

ƒ

This parameter decreases output voltage

according to load status.

0 0

10-

12

F50 [Electronic

thermal
select]

0/1

ƒ

This parameter is activated when the

motor is overheated (time-inverse).

0 0

12-1

2) Only displayed when F24 (Freq High/Low limit select) is set to 1.

3): Set F30 to 2 (User V/F) to display this parameter.

F51
4)

[Electronic
thermal level
for 1 minute]

50/200
[%]

ƒ

This parameter sets max current capable

of flowing to the motor continuously for 1
minute.

ƒ

The set value is the percentage of H33 –

[Motor rated current].

ƒ It cannot be set below F52 –[Electronic

thermal level for continuous].

150 0

12-1

45