LG C Series User Manual

Page 61

Advertising
background image

Chapter 9. Basic functions

z Analog Frequency setting via Potentiometer (V0) on the Keypad

Used to prevent fluctuations in analog input signals caused by noise.

Group

LED Display

Parameter Name

Set

Value

Min/Max

Range

Factory

Defaults

Unit

0.0 [Frequency

Command]

-

-

-

Hz

Drive
group

Frq

[Frequency Mode]

2

0/8 0

I 1

[Filter time constant for V0
input]

10 0/9999

10

I 2

[V0 input minimum voltage]

-

0/10

0

V

I 3

[Frequency corresponding to
I2]

- 0/400 0.0 Hz

I 4

[V0 input max voltage]

-

0/10

10

V

I/O
group

I 5

[Frequency corresponding to
I4]

- 0/400 60.0 Hz

ƒ Set Frq – [Frequency Mode] to 2.
ƒ The set frequency can be monitored in 0.0- [Frequency Command].



I 1: [Filtering time constant for V0 input]

Effective for eliminating noise in the frequency setting circuit.

Increase the filter time constant if steady operation cannot be performed due to noise. A larger

setting results in slower response (t gets longer).

t

Set freq

V0 input



I 2 - I 5: [Min/Max input voltage and corresponding frequency setting]

The corresponding frequency to V0 input voltage is settable.

Example: When setting I 2 - [V0 input minimum voltage] = 2V, I 3- [Frequency corresponding

to I 2] = 10Hz, I 4 - [V0 input max voltage] = 8V and I 5 - [Frequency corresponding to I 4] =

50Hz, the following figure is shown.

Freq.
setting

V0 input

I 2

I 4

I 3

I 5

2V

8V

10Hz

50Hz

61