LG C Series User Manual

Page 70

Advertising
background image

Chapter 9. Basic functions

9.4

Accel/Decel time and unit setting

z Accel/Decel time setting based on Max frequency

Group

LED Display

Parameter Name

Set

Value

Min/Max

Range

Factory

Defaults

Unit

ACC

[Accel time]

-

0/6000 5.0

sec

Drive
group

dEC

[Decel time]

-

0/6000 10.0

sec

Function
group 1

F21 [Max

frequency]

-

0/400

60.0 Hz

H70

[Frequency Reference
for Accel/Decel]

0

0/1 0

Function
group 2

H71

[Accel/Decel Time setting
unit]

- 0/2 1

ƒ Set the desired Accel/Decel time at ACC/dEC in Drive group.
ƒ If H70 is set to 0 {Max frequency}, Accel/Decel time is the time that takes to reach the max freq

from 0 Hz.

ƒ Desired Accel/Decel time unit is settable at the H71.



Accel/Decel time is set based on F21 – [Max frequency]. For instance, if F21 is set to 60Hz,

Accel/Decel time 5 sec, and run frequency 30Hz, time to reach 30Hz would be 2.5 sec.

Run
command

Run Freq.

30Hz

Accel time

Decel time

Max. freq.

60Hz



More precise time unit can be set corresponding to load characteristics as shown below.

Code

Parameter Name

Setting

range

Set

value

Description

0.01~600.00

0

Unit: 0.01 sec.

0.1~6000.0

1

Unit: 0.1 sec.

H71

[Accel/Decel Time
setting unit]

1~60000

2

Unit: 1 sec.

70

Advertising