Chapter 9. Basic functions

z Accel/Decel time based on Run frequency

Group

LED display

Parameter name

Set

value

Min/Max

range

Factory

defaults

Unit

ACC [Accel

time]

- 0/6000

5.0 sec

Drive
group

dEC [Decel

time]

- 0/6000

10.0 sec

Function
group 2

H70

[Frequency reference
for Accel/Decel]

1

0/1 0

ƒ Accel/Decel time is set at the ACC/dEC.
ƒ If you set H70 to 1 {Delta frequency}, Accel/Decel time is the time that takes to reach a target freq

from run freq (Currently operating freq.).



When H70 and Accel time are set to 1 {Delta frequency} and 5 sec, respectively,

(A zone: run freq 10 Hz applied first, B zone: Operating via 10 Hz, different run freq is not issued

C: 30Hz Run freq (in this case, Target freq) issued while 10 Hz run freq is applied. But the preset

accel time 5 sec is maintained. )

Run
command

Freq.

command

5

7

12

Time

[sec]

5 sec

5 sec

10Hz

30Hz

A

B

C

(Run freq.)

(Target freq.)

(Delta freq.)

71