background image

Chapter 10. Advanced functions

10.3 Up-Down operation

Group

LED display

Parameter name

Set

value

Min/Max

range

Factory

defaults

Unit

I20

[Multi-function input
terminal P1 define]

0 2

~ ~

I23

[Multi-function input
terminal P4 define]

15

3

I/O group

I24

[Multi-function input
terminal P5 define]

16

0/24

4

ƒ Select terminals for Up-Down operation among P1 thru P5.
ƒ If P4 and P5 are selected, set I23 and I24 to 15 {Frequency Up command} and 16 {Frequency

Down command}, respectively.

P1

P4

P5

FX : I20 = 0

UP : I23 = 15

CM

DOWN : I24 = 16

P4 (UP)

P5(DOWN)

Frequency

Run
command(FX)