Chapter 10. Advanced functions

Example

Rated frequency= 60Hz

Rated motor RPM= 1740rpm

Motor pole number= 4

Hz

f

s

2

120

4

1740

60

=

×

=

H32- [Rated slip frequency] is 2Hz. Set H32- [Rated slip frequency] to 2.



H33: Enter the motor nameplate rated current



H34: Enter the measured current when the motor is running at rated frequency after

the load is removed. Enter 50% of the rated motor current when it is difficult to

measure the motor no load current.



H36: Enter motor efficiency on the nameplate.



H37: Select load inertia based on motor inertia as shown below.

0

Less than 10 times motor inertia

1

About 10 times motor inertia

H37

[Load inertia rate]

2

Greater than 10 times motor
inertia



As the loads are heavier, the speed gap between rated RPM and synchronous speed

is widening (see the figure below). This function compensates for this inherent slip.

Set the Torque boost value within 2%. Setting it too high may cause motor over-

energizing and lead to error in calculating slip speed.

Synchronous

speed

Motor rated

RPM

RPM

Load

Slip

compensation