Chapter 10. Advanced functions

10.7 PID Control

Group

LED Display

Parameter Name

Set

value

Min/Max

Range

Factory

Defaults

Unit

H40

[Control mode select]

2

0/3 0

-

H50

[PID Feedback select]

- 0/1 0 -

H51

[P gain for PID controller]

- 0/999.9 300.0 %

H52

[Integral time for PID
controller (I gain)]

- 0.1/32.0 300 Sec

H53

[Differential time for PID
controller (D gain)]

- 0.0/30.0 0 Sec

H54

[F gain for PID controller]

0/999.9 0 %

H55

[PID output frequency
limit]

- 0/400 60.0

Hz

Function
group 2

I20~24

[Multi-function input
terminal P1-P5 define]

21 0/24

- -

ƒ Set H40 to 2 {PID Feedback control}.
ƒ Output frequency of the inverter is controlled by PID control for use as constant control of flow,

pressure or temperature.



H50: Select the feedback type of PID controller.

0

{Terminal I input (0 ~ 20 mA)}

H50 [PID

feedback

select]

1

{Terminal V1 input (0 ~ 10 V)}



H51: Set the percentage of output to error. If P Gain is set to 50%, 50% of the error

value will be output.



H52: Set the time needed to output the accumulated error value. Set the time required

to output 100% when the error value is 100%. If H52 - [Integral time for PID controller (I

gain)] is set to 1 sec, 100% is output in 1 sec.



H53: Set the output value corresponding to the variation of the error. The error is

detected by 0.01 sec in C series. If differential time is set to 0.01 sec and the

percentage variation of error is 100 per 1 sec, 1% in 100% is output per 10msec.



H54: PID Feed Forward Gain. Set the gain to add the target value to the PID controller

output.



H55: It limits the output of the PID controller.



I20~I24: To exchange PID, set one of P1-P5 terminal to 21 and turn ON.

87