Gas Line Installation

After leveling, position the insert in the fireplace - holding

it about six inches out from its final location.

Caution: Specific hearth requirements apply (see Clear-

ances to Combustibles).

The Ravenna™ gas insert must be connected to the gas

line in accordance with local codes and/or the National Fuel

Gas Code, ANSI Z223.1 (In Canada, the current CAN/CSA

B149.1 installation code). The insert comes with an 8" nipple

attached to the supply side of the gas valve. After connect-

ing the gas line, all joints in the line and connections at the

valve should be checked for leaks before final positioning of

the unit. Conduct a gas leakage test of the appliance piping

and control system downstream of the shutoff valve in the

supply line to the appliance.

g

as

p

ressure

r

equirements

A MAJOR CAUSE OF OPERATING PROBLEMS WITH GAS

APPLIANCES IS IMPROPER GAS PRESSURE!

The most important item to check during the initial

installation and the first thing to check when operating

problems occur is gas pressure! This appliance will

not function properly unless the required gas pressure

is supplied. See the table on this page for gas pressure

requirements.
Two pressure taps are provided on the insert's valve to

check gas pressures. The taps are located to the right of

the on/off/pilot knob (see Figure 14). The bottom tap is the

inlet (supply) pressure side. To check inlet pressure (with

the insert burning), insert a small phillips screwdriver into

the tap and turn a half turn counter-clockwise. Cover the

tap with the line from a manometer and check the pressure.

Close the tap gently but securely after completing the check.

The manifold (outlet) tap is above the inlet tap. To check

manifold pressure (with the insert burning at the high burn

setting) insert a small phillips screwdriver into the tap and

turn a half turn counter-clockwise. Cover the tap with the

line from the manometer and check the pressure. Again,

close the tap gently but securely after completing the check.

Check the taps for gas leaks with a gas leak test solution

(retighten if necessary).
If the pressure is not sufficient, make sure the gas supply line

is large enough, the supply regulator is properly adjusted,

and the total gas load for the residence does not exceed the

amount supplied.

The appliance and its individual shut off valve must be

disconnected from the gas supply piping system during any

pressure testing of that system at test pressures in excess of

1/ psig.

The appliance must be isolated from the gas supply piping

system by closing its individual manual shut-off valve during

any pressure testing of the gas supply piping system at test

pressures equal to or less than 1/ psig. Check with your gas

supplier or plumber.

lp

and

n

atural

g

as

s

upplies

Your Ravenna gas insert is equipped from the factory for

use with natural gas only as specified on the Safety / Listing

label attached to the appliance. This appliance can only be

operated using propane gas (LP) if a certified fuel conver-

sion kit provided by Lennox Hearth Products is installed by

a qualified service technician.

Also check the orifice size on the label on the igniter bracket.

It must be the correct size for the fuel and altitude.

Do not run propane tank dry. Running the tank dry may

cause a hazardous condition due to pressure drop in

empty tank.

Solid fuel is NOT to be used with this unit.

Air Shutter Adjustment

The Ravenna gas insert has an air shutter control lever

located behind the lower door on the insert's face and to

the left of the gas valve (see Figures 15a & 15b). The lever

is linked to the primary air shutter on the main burner. The

air shutter regulates the amount of primary air the burner

receives and therefore how clean the insert burns. The air

shutter should only be adjusted by a qualified gas techni-

cian. The insert should burn for about 15 minutes with the

logs installed before adjusting the air shutter. More air will

result in shorter flames and less color, less air will result

in bigger flames and more color. To adjust the air shutter,

insert a regular screwdriver into the slide adjustment and

slide it side to side (see Figures 15a & 15b). Caution: The

air shutter should never be set so as to make the tips of

the flames sooty or create sooting on the viewing glass,

logs, or heat exchanger. If soot begins to form after burn-

ing, the air shutter should be opened gradually until the

sooting condition stops. Gas quality and gas pressure

may vary, which can affect the burning characteristics

of the insert.

Fuel

Type

Inlet Pressure

Manifold Pressure

Desired Minimum Maximum

On Hi

Fire

On Lo

Fire

Natural

Gas

7" WC

5" WC

10.5" WC

3.5" WC 1.7" WC

LP Gas

11" WC 10.5" WC

13" WC

10" WC

5.4” WC

Robertshaw Millivolt Gas Valve

TP/TH

TH

TP

Inlet (Supply)

Pressure Tap

Figure 14

The Manifold

(Outlet) Tap