Liebert LM250120YARCE User Manual

Liebert Computer Accessories

Advertising
background image

Liebert Corporation • 1050 Dearborn Drive • PO Box 29186 • Columbus, OH 43229
Phone 607-724-2484 • Fax 607-722-8713 • US & Canada 800-288-6169
EMAIL: info@control-concepts.com • Web Site: www.Liebert.com

82241 Rev 1

Example Part Number:

LM250120YARCE

500kA per Phase (250kA per Mode),
120/208V 3-Phase Wye, All Mode,
Rotary Disconnect, LED’s, Alarm,

Counter, & Dual Form C Contacts,
NEMA 12 Enclosure

Liebert LM Series TVSS

Technical Specification

Maximum Continuous
Operating Voltage (MCOV)
...................... 120V 125%, all others 115%
Fault Current Rating (AIC)....................... 200 kAIC
Operating Frequency Range ................... 47 – 63 Hz
Response Time ........................................ <0.5 ns
Operating Humidity.................................. 0% to 95%
Status Indication ...................................... LEDs, Audible Alarm, Dry Contacts
Certifications ............................................ UL 1449 & 1283, CUL, NEMA LS1,
ISO 9001:2000
Enclosure ................................................ NEMA 12
Warranty ................................................... 5 Years Parts

UL 1449 second edition clamping data

Configuration

L-N

L-G

L-L

N-G

120S, 120Y

400

400

700

400

240D

X

700

700

X

346Y

1200

1200

2000

1200

230Y, 277Y

700

700

1500

700

480D

X

1500

1500

X

600D

X

1800

2000

X

Job Name ____________________________

Model# ______________________________

Date ________________________________

Qty _________________________________

Quote# ______________________________

Source Configuration

1 Phase, L-N, 2W+G

N

1 Phase, L-L, 2W+G

L

Split Phase, 3W+G

S

3 Phase, WYE, 4W+G

Y

3 Phase, WYE, 3W+G

(No Neutral)

X

3 Phase, Delta, 3W+G

D

3 Phase, Delta Hi-leg, 4W+G

H

Surge Rating

60kA /
mode

060

80kA /
mode

080

100kA /
mode

100

125kA /
mode

125

150kA /
mode

150

200kA /
mode

200

225kA /
mode

225

250kA /
mode

250

Model # LM

__ __ __ __ __ __ __ __ __ __ __

Modes of Protection

All

A

L-G Voltage

120V

120

208V

208

220V

230

230V

230

240V

240

277V

277

480V

480

600V

600

Connection Options

Wire Lug

N

Disconnect

R

Enclosure

NEMA 12

(Standard)

E

NEMA 3R

R

NEMA 4

T

NEMA 4X

X

Monitoring Options

Standard Monitoring System,
LEDs, Audible Alarm,
Dual Form C Contacts

S

LEDs, Audible Alarm,
Surge Counter,
Dual Form C Contacts

C

Dimensional data in inches and shipping weight in pounds

Unit

Options

A

B

C

D

E

F

G

Wt.

LM060
LM080

All

16

14

8

16.75

12

0.31

1.35

32

LM100
LM125
LM150

All

16

14

8

16.75

12

0.31

1.84

41

LM200
LM225
LM250

All

20

16

9

21.25

10

0.44

1.84

56

Life Cycle Surge Testing

10kA, 20kV, IEEE Cat. C3

Unit

Per Mode

Per Phase

060-080

8,000

16,000

100-150

16,000

32,000

200-250

24,000

48,000

EMI/RFI Noise Rejection

Single

Unit

Frequency

System

Installation

34dB

100kHz

51dB

51dB

1MHz

94dB

54dB

10MHz

114dB

48dB

100MHz

120dB

E

D

C

B

G

A

F

Advertising