Gas supply – Langley/Empire MV 130 User Manual

Page 6

Advertising
background image

Figure 2

GAS SUPPLY

Compounds used on threaded joints of gas piping shall be
resistant to the action of liquefied petroleum gases. The gas
lines must be checked for leaks by the installer. This should be
done with a soap solution watching for bubbles on all exposed
connections, and if unexposed, a pressure test should be made.

Never use an exposed flame to check for leaks. Appliance
must be disconnected from piping at inlet of control valve
and pipe capped or plugged for pressure test. Never
pressure test with the appliance connected; control valve
will sustain damage!

A gas valve and ground joint union should be installed in the
gas line upstream of the gas control to aid in servicing. It is
required by the National Fuel Gas Code that a drip line be
installed near the gas inlet. This should consist of a vertical
length of pipe tee connected into the gas line that is capped on
the bottom in which condensation and foreign particles may
collect.

Pressure Testing of the Gas Supply System

1. To check the inlet pressure to the gas valve, a 1/8" (3 mm)

N.P.T. plugged tapping, accessible for test gauge
connection, must be placed immediately upstream of the
gas supply connection to the appliance.

2. The appliance and its individual shutoff valve must be

disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess of
1/2 psig (3.5 kPa).

3. The appliance must be isolated from the gas supply piping

system by closing its individual manual shutoff valve
during any pressure testing of the gas supply piping system
at test pressures equal to or less than 1/2 psig (3.5 kPa).

Attention! If one of the above procedures results in pressures
in excess of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas
valve, it will result in a hazardous condition.

Checking Manifold Pressure

Both Propane and Natural gas valves have a built-in pressure
regulator in the gas valve. Natural gas models will have a
manifold pressure of approximately 4.0" w.c.(0.996 kPa) for
MV120 and 130 or 6.0" w.c.(1.494 kPa) for MV145 at the
valve outlet with the inlet pressure to the valve from a
minimum of 5.0" w.c.(1.245 kPa) for MV120 and 130 or 7.0"
w.c.(1.742 kPa) for MV145 for the purpose of input
adjustment to a maximum of 10.5" w.c.(2.61kPa). Propane gas
models will have a manifold pressure approximately 10.0"
w.c.(2.49kPa) at the valve outlet with the inlet pressure to the
valve from a minimum of 11.0" w.c.(2.739kPa) for the purpose
of input adjustment to a maximum of 13.0" w.c.(3.237kPa). A
1/8" (3mm) N.P.T. plugged tapping, accessible for test gauge
connection, is located on the outlet side of the gas control.

Locating Gas Supply

The gas line can enter the unit either through the floor or
outside wall. The gas line opening should be made at this time.
Location of the opening will be determined by the position of
floor joists and the valve and union used for servicing.

Recommended Gas Pipe Diameter

Note: Never use plastic pipe. Check to confirm whether your
local codes allow copper tubing or galvanized.

Note: Since some municipalities have additional local codes,
it is always best to consult your local authority and installation
code.

The use of the following gas connectors is recommended:

— ANS Z21.24 Appliance Connectors of Corrugated Metal

Tubing and Fittings

— ANS Z21.45 Assembled Flexible Appliance Connectors of

Other Than All-Metal Construction

The above connectors may be used if acceptable by the
authority having jurisdiction. The state of Massachusetts
requires that a flexible appliance connector cannot exceed
three feet in length.

Consult the current National Fuel Gas Code, ANSI Z223.1
CAN/CGA-B149 (.1 or .2) installation code.

Installing a New Main Gas Cock

Each appliance should have its own manual gas cock. In the
state of Massachusetts the gas cock must be a T handle type. A
manual main gas cock should be located in the vicinity of the
unit. Where none exists, or where its size or location is not
adequate, contact your local authorized installer for
installation or relocation.

Pipe Lenght

(Feet)

Schedule 40 Pipe

Inside Diameter

Tubing, Type L

Outside Diameter

Nat.
1/2”

1.3 cm

5/8”

1.6 cm

3/4”

1.9 cm

7/8”

2.2 cm

L.P.

3/8”

1.0 cm

1/2”

1.3 cm

1/2”

1.3 cm

3/4”

1.9 cm

0 - 10

10 - 40

40 - 100

100 - 150

Figure 1

3” (76 mm)

DRIP LEG

Alternate locations

for shut off valve

Gas supply inlet

NPT Niple

NPT Niple

Close Niple

Shut Off

Valve

NPT Gas

Supply

NPT Union

Flare Fitting

Flex

Tubbing

Flare Shut

Off Valve

Gas

Supply

Tee

Handle

Tee Handle

FLEXIBLE GAS LINE CONNECTION

RIGID GAS LINE CONNECTION

Page 6

L.P.

3/8”

1.0 cm

1/2”

1.3 cm

1/2”

1.3 cm

1/2”

1.3 cm

Nat.
1/2”

1.3 cm

1/2”

1.3 cm

1/2”

1.3 cm

3/4”

1.9 cm

MV1XX-2-0404

Advertising
This manual is related to the following products: