Lakeshore Learning Materials 647 User Manual

Page 52

Advertising
background image

Lake Shore Model 647 Magnet Power Supply User’s Manual

Troubleshooting

5-2

No delay is allowed (CAL AND ID switch 7 OFF,

down) and multiple MPS operation (CAL AND ID

switch 4 ON, up) must be selected. After the load

discharges, turn OFF all units to reset. The MPS

displays the OVP error message.

Overvoltage Protection (OVP) Circuit Activated

If the voltage across the MPS output terminals

rises above ±40 volts, the output over voltage

protection (OVP) circuit activates. The MPS also

may activate the OVP circuit in response to faults.

Upon activation, the OVP circuit uses thyristors to

crowbar the output voltage to between 1 and 1.3

volts until magnet current reaches zero. If this

occurs, change the output current setting to zero.

If the MPS detects OVP activity on power up

(output current greater than ±1 A), it turns ON the

front panel Fault annunciator, closes FLT

contacts, and sounds the alarm twice per second.

When the MPS detects the fault, it closes the FLT

contacts to indicate a fault, sounds the alarm once

per second, and displays:

O V E R V O L T A G E P R O T E C T IO N :

T H E O U T P U T S E T T IN G S A R E
F O R C E D T O 0 A A N D 1 V .

O V P IS A C T IV E U N T IL T H E

O U T P U T C U R R E N T F A L L S
B E L O W 1 A .

O U T P U T :

*

- 0 .0 0 A

+ 1 .0 0 V

O V P L O C

When output current falls below 1 A, the MPS

turns OFF the front panel Fault annunciator and

alarm, and opens the FLT contacts. When the

MPS detects no OVP activity, the Normal Display

appears.

The MPS continues to display OVP and sounds

the alarm until the user enters new output settings,

then turns them OFF. This latching action informs

the user of OVP activity. The MPS opens the FLT

contacts upon detecting OVP inactivity.

Low AC (LO AC) Detected

If the AC line falls below 80% of the nominal line

selected, the MPS enters AC Loss Mode. If this

occurs on power up, the MPS turns off the front

panel circuit breaker and displays:

T H E U N IT W IL L B E T U R N E D
O F F T O A V O ID D A M A G E .
V E R IF Y A C IN P U T S E T T IN G .

O U T P U T :

*

- 0 .0 0 A

+ 1 .0 0 V

L O A C L O C

L O A C IN P U T

L IN E F A U L T :

This indicates that the AC source does not match
the line voltage listed on the rear panel.

Upon utility loss during normal operation of a

single MPS with a charged load, the MPS disables

utility input circuitry and uses the load as an

energy source. It turns OFF the front panel Power

annunciator and turns ON the front panel Fault

annunciator. It closes the FLT contacts to indicate

a fault and sounds the alarm about once per second.

The MPS sets output voltage compliance to the level

required to maintain operation and continuously

monitors output current. If the utility recovers, the MPS

enters Remote Inhibit Mode and forces output settings

to 0 amps and 1 volt. If the utility does not recover, the

MPS activates the output OVP circuit and turns OFF

the front panel circuit breaker when the output current

drops below 10 amps. Upon power down, the MPS

enters AC Loss Mode.

NOTE: A utility loss while the MPS returns energy

from a charged load to the utility presents no hazard to

personnel working on the utility circuit. The MPS is not

a UPS. It uses the utility voltage wave form to draw

energy from the utility with a sinusoidal current and

return energy to the utility with a sinusoidal current. If

there is no utility reference signal, the MPS disables

utility input circuitry and uses the load for energy.

If utility loss occurs during normal operation in a

multiple MPS configuration, the MPS detecting the

utility loss initiates Multiple MPS Remote Inhibit Mode

by closing the FLT contacts and turning off the front

panel circuit breaker. Then the remaining MPS units

enter Multiple MPS Remote Inhibit Mode.

High AC (HI AC) Detected

Any time the AC line rises above 120% of the nominal

line selected, the MPS turns off the front panel circuit

breaker and enters AC Loss Mode. This halts

excessive utility voltages to internal circuitry. If this

occurs on power up, the MPS turns off the front panel

circuit breaker and displays:

- 0 .0 0 A

+ 1 .0 0 V

H IA C L O C

T H E U N IT W IL L B E T U R N E D
O F F T O A V O ID D A M A G E .
V E R IF Y A C IN P U T S E T T IN G .

O U T P U T :

*

H I A C IN P U T

L IN E F A U L T :

Overtemperature Detected
If the MPS detects internal over temperature or other

internal fault, it activates the OVP circuit, turns off the

front panel circuit breaker, and then turns itself off.

OVP stays active until it completely discharges the

load. If the heat sink temperature exceeds 95 °C (203

°F), the MPS displays:

- 0 .0 0 A

+ 1 .0 0 V

T E M P L O C

T H E U N IT W IL L B E T U R N E D
O F F T O A V O ID D A M A G E .
IN T E R N A L T E M P T O O H I.

O U T P U T :

*

IN T E R N A L

T E M P F A U L T :

Advertising