Troubleshooting – LG LENNOX MPB3328CNE User Manual

Page 23

Advertising
background image

23

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

TROUBLESHOOTING GUIDE - MILLIVOLT GAS CONTROL SYSTEM

Note: Before troubleshooting the gas control system, Ensure external gas shut off valve, located at gas supply inlet, (and wall switch, iff applicable), is
in the “ON” position. Important: Valve system troubleshooting should only be accomplished by a qualifi ed service technician.

SYMPTOM

POSSIBLE CAUSES

CORRECTIVE ACTION

1. Spark Igniter will not light pilot after

repeated triggering of Igniter button.

A. Defective igniter

(no spark at electrode).

Check for spark at electrode and pilot; if no spark
and electrode wire is properly connected, replace
Igniter.

B. Defective or misaligned electrode at pilot

(spark at electrode).

Using a match, light pilot. If pilot lights, turn off pilot
and trigger the igniter button again. If pilot lights, an
improper gas mixture caused the bad lighting and
a longer purge period is recommended. If pilot will
not light – check gap at electrode and pilot – should
be 1/8" to have a strong spark. If gap measures 1/8",
replace pilot (see Figure 8 on Page 8).

C. Gas supply pressure errant.

Check inlet gas pressure. It should be within the limits
as marked on the rating plate.

D. Pilot orifi ce plugged.

Clean or replace pilot orifi ce.

2. Pilot will not stay lit after

carefully following the lighting
instructions.

A. Defective pilot generator
(thermocouple).

Check pilot fl ame, it must impinge on thermocouple
(see Figure 8 on Page 8). Clean and/or adjust pilot
for maximum fl ame impingement on thermocouple.
Ensure that the connection between the valve and
thermocouple are tight and secure.

3. Pilot burning, no gas to burner, Valve

knob “ON,” Wall Switch “ON.”

A. Limit Switch defective.

Isolate the “limit” switch. Disconnect the wires from
the “ON/OFF” switch and the valve (label wires for
reattachment). Test for continuity with a multimeter.
If continuity is not indicated, switch is defective and
must be replaced.

B. Wall switch or wires defective.

Check wall switch and wires for proper connections.
Jumper wire across terminals at wall switch, if burner
comes on, replace defective wall switch. If okay, jumper
wires across wall switch wires at valve, if burner comes
on, wires are faulty or connections are bad.

C. Thermopile may not be generating suf-

fi cient millivoltage.

Check thermopile with millivolt meter. Take reading
at thermopile terminals of gas valve. Should read
325 millivolts minimum with optional wall switch
“OFF.” Replace faulty thermopile if reading is below
specifi ed minimum.

D. Plugged burner orifi ce.

Check burner orifi ce for stoppage and remove.

4. Frequent pilot/burner outage prob-

lem.

A. Pilot fl ame may be too low or blowing (high)

causing the pilot/valve safety to drop out.

Clean and/or adjust pilot fl ame for maximum fl ame
impingement on thermocouple (see Figures 8 on
Page 8)
.

TROUBLESHOOTING

SYMPTOM

POSSIBLE CAUSES

CORRECTIVE ACTION

1. Burner will not light.

A. Faulty Valve System.

See Below.

B. “OFF/ON” or wall switch defective.

Disconnect the two black wires from the wire nuts.
Test switch(s) for continuity with a multimeter. If
continuity is not indicated, switch(s) is defective and
must be replaced.

Note: Before replacing “OFF/ON” switch, Ensure to
check wiring for loose connections or broken wires
and repair as needed.

2. Burners come “ON,” then turns “OFF.”

A. Burner orifi ce plugged.

Check main burner orifi ce(s) for blockage. Clean
or replace.

B. Obstructed vent system.

Check vent system for obstructions.

TROUBLESHOOTING GUIDE - ELECTRONIC IGNITION SYSTEM