LG K7F-PIDA User Manual

Page 27

Advertising
background image

Chapter 5. DEDICATED INSTRUCTIONS FOR SPECIAL MODULES

5 - 2

5.2 Write to Buffer Memory

⋅⋅⋅⋅

⋅⋅⋅⋅

⋅⋅⋅⋅

PUT, PUTP

<Format> execution condition

for PUT

Format

Descriptions

Available Data Type

n1

The slot No. where a special module is mounted.

Integer

n2

Head address of the special module buffer memories to which the
data will be written..

Integer

D

Head address of the device where the data to be written has been

stored, or an integer

M,P,K,L,T,C,D,#D

n3

Number of data to be written.

Integer

<The difference between PUT and PUTP>

PUT: always executed if the execution condition turns on. ( )

PUTP : executed if the execution condition is triggered. ( )

Example 1) In this example, the PID control module is mounted on the slot 6 in the base unit and the data of

CPU module addresses D0 and D1 will be written to the buffer memory addresses D202 and D203.

(address) CPU module D area

PID control module

buffer memory (address)

D0

Data 0

Specify the enabled loop

0

D1

Data 1

Specify the enabled loop

1

D2

2

D3

3

D2

4

<PUT>


execution condition
for PUT

execution condition

<PUTP> for PUTP

M0000

PUT n1 n2 S n3

PUT 00006 00000 D0000 00002

D M0000

PUTP 00006 00202 D0000 00002

Advertising