2 performance specifications – LG K7F-PIDA User Manual

Page 9

Advertising
background image

Chapter 2. SPECIFICATIONS

2 - 2

2.2 Performance Specifications

Table. 2.2 shows performance specifications of the PID control module.

Specifications

Items

K7F-PIDA

K4F-PIDA

Proportional constant (P)

0.01 ~ 100.00

( When integral and derivative constants are set to

0.0 sec, proportional action is applied.)

Integral constant (I)

0.0 ~ 3000.0 sec

( When integral constant is set to 0.0 sec, integral action

shall not be applied.)

Setting range

of PID

constants

Derivative constant (D)

0.0 ~ 3000.0 sec

( When derivative constant is set to 0.0 sec, derivative

action shall not be applied.)

Setting range : SV (Set Value)

0 ~ 16,000

Input range : PV (Process Value)

0 ~ 16,000

Output range : MV (Manipulated Value)

0 ~ 16,000

Setting range : M_MV

(Manually Manipulated Value)

0 ~ 16,000

RUN / STOP

RUN : The run LED of corresponding loops ON

STOP : The run LED of corresponding loops OFF

LED

NORMAL/ERROR

Normal : RUN LED ON

Error : RUN LED flickering

Number of PID control loops

32 loops

8 loops

Control action

Forward/Reverse action control is available.

Control cycle

0.1 sec

Processing type

Measured value derivative type

(Pre-derivative type)

Internal current consumption

0.3 A

0.2 A

Weight

370 g

190 g

[Table. 2.2 Performance Specifications]