UL 1449 second edition clamping data

Voltage

L-N

L-G

L-L

N-G

100-120V 400 400 800 400

208V

800

800

230-277V 800 800 1500 700

347V 1200

1000

2000

1000

400-480V 1500

1500

600V

2000

2000

Liebert Active Tracking Filter System

Technical Specification

Operating Voltage Range ......................................... +/-15%

Fault Current Rating (AIC)........................................ 200 kAIC

Operating

Frequency

Range.................................... 47 – 63 Hz

50

EMI/RFI Attenuation:

Normal Mode .............................................. 10 kHz-500MHz 60 dB

Common Mode ........................................... 10 kHz-500MHz 50 dB

Response

Time ......................................................... <0.5 ns

Operating

Humidity................................................... 0% to 95%

Status

Indication ....................................................... LEDs, Dry Contacts, Audible Alarm,

Surge

Counter

Certifications ............................................................. UL 1449 & 1283, CSA
Enclosure

.................................................................. NEMA 12 standard

Warranty

.................................................................... 10-Years Parts / 5-Years Labor

Optional

Equipment.................................................. Dual Surge Counter,

Remote

Monitor

Panel

Dimensional data in inches and shipping weight in pounds

Model/Configuration

Dimensions in inches

Wt

A

B

C

D

E

F

Lbs

30A Single Phase

20.0

16.0 9.0 21.25 10.0 .44 35

30A Split or Three Phase

24.0 20.0 9.0 25.25 14.0 .44 60

60A Single Phase

20.0

16.0 9.0 21.25 10.0 .44 35

60A Split or Three Phase

24.0 20.0 9.0 25.25 14.0 .44 60

100A Single Phase

24.0

20.0 9.0 25.25 14.0 .44 60

100A Split or Three Phase

30.0 24.0 9.0 31.25 18.0 .44 80

225A Single Phase

24.0

20.0 9.0 25.25 14.0 .44 60

225A Split or Three Phase

30.0 24.0 9.0 31.25 18.0 .44 80

400A Split or Three Phase

48.0 36.0 12.0 49.25 30.0 .44 300

800A Split or Three Phase

60.0

48.0

12.0

-

-

-

530

1200A Split or Three Phase

60.0

48.0

20.0

-

-

-

750

2000A Split or Three Phase

60.0

48.0

20.0

-

-

-

950

4000A Split or Three Phase

60.0

48.0

20.0

-

-

-

1300

Nominal

Voltage Codes

120

120V

208

208V

220

220V

230

230V

240

240V

277

277V

480

480V

600

600V

Source configuration

N

1 Phase L-N 2w + gnd

L

1 Phase L-L 2w + gnd

S

Split Phase 3w + gnd

Y

3 Phase Wye 4w + gnd

D

3 Phase Delta 3w + gnd

H

3 Phase Delta Hi-leg 4w+ gnd

F__ __ __ __ __ __ __ __ - __ __

Option Code

01

LED, Form C

Contacts

03

LED, Alarm, Dual

Counters, Form C

Contacts

06

LED, Alarm, Counter,

Form C Contacts

Example Part Number:

F277Y800-03

= 277/480V, 3-Phase Wye, All Mode, 800 Amp Current Rating

LED’s, Alarm & Dual Counters, Form C Contacts

Current

Code

Current

Rating

Surge Current Capability

Per Phase

30

30A 100kA

60

60A 100kA

100

100A 150kA

225

225A 150kA

400

400A 150kA

800

800A 300kA*

1200

1200A 300kA*

2000

2000A 300kA*

4000

4000A 300kA

* 200kA is available,

add –200 to part number.

Job Name____________________________

Model# ______________________________

Date ________________________________

Qty _________________________________

Quote# ______________________________

Life Cycle Surge Testing

10kA, 20kV, IEEE Cat. C3

Unit

Per Mode (L-N/L-G/N-G)

Per Phase

100 kA

12,000/12,000/12,000

24,000

150 kA

12,000/24,000/24,000

36,000

200 kA

24,000/24,000/24,000

48,000

300 kA

24,000/48,000/48,000

72,000

Advertising