NOTE: DIAGRAMS AND ILLUSTRATIONS ARE NOT TO SCALE

We recommend that a qualified individual such as a plumber or gas fitter be

used to correctly size and route the gas supply line to the appliance. Installing

a gas supply line from the fuel supply to the appliance involves numerous

considerations of materials, protection, sizing, locations, controls, pressure,

sediment, and more. Certainly no one unfamiliar and unqualified should attempt

sizing or installing gas piping. Never use galvanized or plastic pipe.

The gas supply line should be plumbed from the fuel source to the area

where the appliance is to be installed per requirements outlined in NFPA

54 - latest edition (USA) or CAN/CSA B149.1 - latest edition (Canada)

and per local codes.

The insert comes with an 8 inch (203 mm) nipple attached to the supply

side of the gas valve. After connecting the gas line, all joints in the line

and connections at the valve should be checked for leaks using a gas

leak test solution before final positioning of the unit.

Gas Pressure Requirements

It is important to check the gas pressure during the initial installation

of the insert and ensure there are no operating problems. This insert

will not function properly unless the required gas pressure is supplied.

Two pressure taps are provided on the insert's valve to check gas pres-

sures (see

Figure 37 on Page 22). The taps are located to the left of the

on/off/pilot knob. The top tap is the inlet (supply) pressure side. To check

inlet pressure (with the fireplace insert burning), insert a small regular

screwdriver into the tap and turn a half turn counterclockwise. Cover the

tap with the line from a manometer and check the pressure. Close the tap

gently but securely after completing the check. The manifold (outlet) tap

is below the inlet tap. To check manifold pressure (with the insert burning

at the high burn setting) insert a small phillips screwdriver into the tap

and turn a half turn counterclockwise. Cover the tap with the line from

the manometer and check the pressure. Again, close the tap gently but

securely after completing the check. Check the taps for gas leaks with a

gas leak test solution and retighten if necessary.

If the pressure is too low, make sure the gas supply line is large enough,

the supply regulator is properly adjusted, and the total gas load for the

residence does not exceed the amount supplied.

IMPORTANT NOTE: If propane is used, be aware that if the tank size is too

small (i.e. under 100-lbs, if this is the only gas appliance in the dwelling.

Ref. NPFA 58), there may be loss of pressure, resulting in insufficient fuel

delivery (which can result in sooting or other malfunctions). Any damage

resulting from an improper installation, such as this, is not covered under

the limited warranty.

LP and Natural Gas Supplies

Your

Shoreline™ can be operated with either natural gas or liquid

propane (LP). It is shipped from the factory for use with only natural

gas. The fireplace insert must always be operated with the same gas as

specified on the label unless converted by a qualified service technician

as per this manual.

Also check the orifice size on the label located below the Shoreline insert.

It must be the correct size for the fuel and altitude.

Inlet Gas Supply Pressure

Fuel #

Minimum

Maximum

Desired

Natural

Gas

5" WC/po. C.E

(1.5 kPa)

10.5" WC/po. C.E

(.61 kPa)

7" WC/po. C.E

(1.74 kPa)

Propane 10.5" WC/po. C.E

(.61 kPa)

13.0" WC/po. C.E

(3.3 kPa)

11" WC/po. C.E

(.74 kPa)

Table 10

Manifold Gas Supply Pressure

Fuel #

Low

High

Natural Gas

(Lo) 1.3" WC/po. C.E

(.3 kPa)

(Hi) 3.5" WC/po. C.E

(.87 kPa)

Propane

(Lo) 5.4" WC/po. C.E

(1.35 kPa)

(Hi) 10.0" WC/po. C.E

(.49 kPa)

Table 11

These appliances and their individual shut-off valves must be discon-

nected from the gas supply piping system during any pressure testing

of that system at pressures greater than 1/2 psig (3.5 kPa).

These appliances must be isolated from the gas supply piping system

(by closing their individual manual shut-off valve) during any pressure

testing of the gas supply piping system at test pressures equal to or

less than 1/2 psig (3.5 kPa).

Tables 10 and 11 show the units' gas pressure requirements for

these appliances.

GAS LINE INSTALLATION

Pre-Lighting Checklist

Be sure to check these items before the initial lighting of the insert:

_____ The insert gas label corresponds to the gas supply available

- that is "natural gas" for natural gas or "LP gas" for LP gas.

_____ Gas pressure has been checked carefully.
_____ All gas fittings have been checked for leaks.
_____ All clearances to combustibles have been met.
_____ All combustible materials have been removed from the area

in front of the insert.

_____ All vented areas of the insert face are unobstructed.
_____ House is ventilated to clear initial curing odor.
_____ All packaging materials have been removed from the fire-

box.

_____ While insert is cool, fingerprints or other marks should be

cleaned from any surfaces with a soft cloth. Marks left on these

surfaces may become etched into the finish if not removed

prior to burning the unit.

_____ Brick panels and log set have been installed.
_____ The glass door is in place and is properly sealed.