Lochinvar ARMOR 151-200 User Manual

Pump, Pump specifications, Installation specifications

Advertising
background image

1



PUMP RECOMMENDATION FOR

ARMOR 151-200 WATER HEATER

Pump Specifications

Part No.

HorsePower

Flanges

Valute Material

Flange Material

Vendor

Vendor Product Series

Orientation

PUM3010

1/6

1-1/4"

Bronze

Bronze

Armstrong

E Series

Vertical


Installation Specifications

Recommended for

Based on

Pump

Model Numbers

Minimum GPM

Installation Type

Armor Wtr Htr, AW(N,L) 151-200

16 GPM (151) & 21 GPM (200)

Single Water Heater piped to Single Storage Tank

PUM3010

Based on

Based on

Minimum Pipe Diameter

Connecting piping

1-1/4"

Maximum 45 feet straight pipe with 4-Elbows, 2-Unions and 2-Ball Valves

IMPORTANT: Read the Armor 151-801 Installation and Operation Manual. If the planned system exceeds
the pump capacity in flow and/or head see

“Pump Curves-All Pumps” for alternate pumps and pump curves.

























PUMP

Recommendation

PUMP-Rec-01 Rev C

Advertising