Burner setup & boiler operation – PB Heat WV Series User Manual

Page 17

Advertising
background image

15

BURNER SETUP & BOILER OPERATION

BECKETT BURNER SPECIFICATIONS

Boiler

Model No.

Burner

Model No.

Burner

Head

Static

Plate

Nozzle Size

Pump

Pressure

Start-up Settings

Head

Setting

Air Shutter

Air Band

WBV-03-085

AFG-F3¹

F3

3-3/8"

0.75 80° B HAGO³

140 PSI

6.0

1

N/A

WBV-03-105

AFG-F4

F4

3-3/8"

0.90 80° B HAGO

140 PSI

6.0

0

N/A

WBV-04-095

AFG-F4

F4

3-3/8"

0.85 80° B DEL

4

140 PSI

6.0

0

N/A

WBV-04-125

AFG-F4

F4

3-3/8"

1.10 80° B HAGO³

140 PSI

5.0

2

N/A

WBV-04-150

AFG-F6

F6

2-3/4"

1.25 80° B HAGO

140 PSI

8.0

1

N/A

WV-05-175

AFG-MV1

V-1

-

1.50 60° B HAGO³

140 PSI

10.0

3

3

WV-05-195

AFG-MV1

V-1

-

1.65 60° B HAGO

140 PSI

10.0

9

3

CARLIN BURNER SPECIFICATIONS (WITH 98022 PSC MOTOR)

Boiler

Model No.

Burner

Model No.

Head Bar

Nozzle Size

Pump Pressure

Start-up Settings

Air Shutter

Air Band

WBV-03-085

EZ-1HP

0.60 - 0.65

0.65 70° A DEL³

150 PSI

Blank

0.60

WBV-03-105

EZ-1HP

0.85 - 1.00

0.85 70° A DEL

150 PSI

Blank

0.65

WBV-04-095

EZ-1HP

0.75

0.75 70° A DEL

4

150 PSI

Blank

0.60

WBV-04-125

EZ-1HP

0.85 - 1.00

1.00 70° A DEL³

150 PSI

Blank

0.85

WBV-04-150

EZ-1HP

1.10 - 1.25

1.25 60° B DEL

150 PSI

Blank

1.00

WV-05-175

99FRD

N/A

1.50 60° B HAGO³

150 PSI

Open

10% open

WV-05-195

99FRD

N/A

1.65 60° B HAGO

150 PSI

Open

45% open

RIELLO BURNER SPECIFICATIONS

Boiler

Model No.

Burner

Model No.

Burner Series

Nozzle Size²

Pump Pressure

Start-Up Settings

Turbulator

Air Damper

WBV-03-060

F3

Series 40

0.50 90° B

145 PSI

0.0

2.9

WBV-03-085

F5

Series 40

0.65 60° W³

170 PSI

1.0

2.45

WBV-03-105

F5

Series 40

0.85 60° W

165 PSI

2.5

2.8

WBV-04-095

F5

Series 40

0.75 80° B

4

160 PSI

0.5

2.25

WBV-04-125

F5

Series 40

1.00 60° W³

155 PSI

2.5

3.4

WBV-04-140

F5

Series 40

1.10 60° W

160 PSI

4.0

4.2

WV-05-175

F10

Series 40

1.35 60° B³

165 PSI

2.0

2.5

WV-05-195

F10

Series 40

1.50 60° B

170 PSI

2.5

2.8

Factory Installed Nozzles (Packaged Boilers or Burner Cartons) are indicated in Boldface.
1 Requires Low Firing Rate Baffle
2 Delavan Recommended
3 Shipped Loose with Packaged Boiler or Burner Carton
4 Not included with Packaged Boiler or Burner Carton

Table 5.1:

Beckett Burner Specifications

Table 5.2:

Carlin Burner Specifications (with 98022 PSC motor)

Table 5.3:

Riello Burner Specifications

BECKETT NX BURNER SPECIFICATIONS

Boiler Model No.

Burner Model

Nozzle Size

Pump Pressure

Start Up Head/Air

WBV-03-085

NX70LB

0.65 x 60° W DEL³

170

1.5

WBV-03-105

NX70LB

0.85 x 60° B HAGO

170

2.5

WBV-04-095

NX70LB

0.75 x 60° W DEL

4

170

2.0

WBV-04-125

NX70LD

1.10 x 60° W DEL³

140

1.0

WBV-04-150

NX70LD

1.25 x 60° W DEL

140

2.0

Note: Burner used to fire the WBV-03-.085 and 1.05 rate is also required to fire the WBV-04-.95 rate with nozzle indicated in above chart.