Paradox Hellas S.A. DIP Switches CAA470A-EI02 User Manual

Paradox Hellas S.A. Hardware

Advertising
background image

CAA470A-EI02
PRINTED IN CANADA 07/2004

Introduction

Connected to the CT-V900 controller’s expansion bus, the
2-Door Expansion Module (CA-A470-A) supports two
readers, two BCD keypads, four zone inputs, 6 outputs
and two locking devices.

Specifications

DIP Switches

In order for new DIP switch settings to take effect,
the 2-Door Expansion Module’s power must be
disconnected and then reconnected.

Assign Address (1 and 2)

DIP switches 1 and 2 determine the 2-Door
Expansion Module’s address in the network,
regardless of the order that they are connected
to the controller. Centaur recognizes the doors
according to the DIP switch settings as shown in
Figure 1.

Figure 1: Setting the network address

Lock State during Communication Failure

DIP switches 3 and 4 determine the state of
Lock #1 and Lock #2 ONLY during a
communication failure between the 2-Door
Expansion Module and the controller (CT-V900-
A). Normally, the lock outputs follow the Lock
Control for the CT-V900-A. Therefore, the DIP
switches should have the same setting as the Lock
Control for the corresponding doors in Centaur.

De-energized: no power in normal state; requires
power to activate.

Energized: power in normal state; remove power
to activate.

Access during Communication Failure (5 and 6)

DIP switches 5 and 6 determine the access to
the protected doors during a communication
failure.

Activate Output on Communication Failure (7)

DIP switch 7 determines if OUT5 and OUT6 will
pulse during a communication failure. When DIP
switch 7 placed in the

ON

position, the outputs on

the device(s) connected to the OUT5 and OUT6
terminals will pulse. For example, the LED on
the reader can pulse to advise users that a
communication failure has occurred.

DIP Switch (8)

For future use.

EOL Jumper

Place the EOL jumper ON if the 2-Door Expansion Module
is at the beginning (Start Point) or at the end (End Point) of
the E-bus Network (see Figure 2). Otherwise, place the
EOL jumper OFF.

Figure 2: Setting the Jumpers

High/Low Bias Jumpers

Place the A+ and B- jumpers on LOW only if the 2-Door
Expansion Module is at the beginning (Start Point) of the
E-bus Network. Otherwise, place the A+ and B- jumpers
on HIGH (see Figure 2 and Figure 3).

Figure 3: Setting the A+ and B- jumpers

350mA/700mA Battery Charging Jumper

The 350mA/700mA Jumper allows you to select the
charging current for the backup battery of the 2-Door
Expansion Module. Charging the battery at 350mA takes
longer, but consumes less power. Charging the battery at
700mA takes less time, but consumes more power.

Figure 4: Setting the 350mA/700mA jumper

Programming in Centaur

Using the Centaur Access Control Software, program the
inputs, outputs, readers, and keypads connected to the 2-
Door Expansion Module. The options are explained in the
Centaur Access Control Software Reference Manual.

Centaur will identify the 2-Door Expansion Module by its
address (see DIP Switches 1 to 4) and will recognize the
devices as follows:

Doors cannot be defined as Door Type Elevator
(Door Properties window, General tab, Door
Type
: Elevator) and the module does not support
Interlock Inputs (Door Properties window, Inputs
and Outputs
tab, Interlock Input).

Other modules in the system cannot activate the 2-
Door Expansion Module’s outputs.

The 2-Door Expansion Module does not support
Zone Doubling (see Figure 6).

CA-A470-A Specifications:

Readers:

connect 2 per module

Keypads:

connect 2 per module

Inputs:

4 standard without ATZ, 1 tamper

Outputs:

6 (open collector)

Lock Outputs:

2 lock outputs (Form C relays)
each: 15A @ 16VDC (resistive)

AC Power:

16VAC, 40VA max.

Frequency:

50Hz/60Hz

Aux. Current:

500mA (max.)

Battery:

12VDC, 7Ah
low battery = 10.2VDC
low battery restore = 12.2VDC
low battery cut-off = 8.5VDC

Communication:

expansion bus (E-Bus), RS-485, Plug
and Play, 3 modules per CT-V900

Operating temp.: 5

o

C to 55

o

C (41

o

F to 133

o

F)

2-Door Expansion Module

CA-A470-A

Instructions

780 Industriel Blvd., Saint-Eustache (Quebec) J7R 5V3 CANADA
Tel.: (450) 491-7444 Fax: (450) 491-2313

www.paradox.ca

Lock #1 = DIP switch 3
Lock #2 = DIP switch 4

OFF =

De-energized:
During a communication failure, the normal state of
the lock output is De-energized. When Lock #1 or
Lock #2 is activated, power is applied to the
corresponding lock output to unlock the door.
Activation depends on the setting of the DIP switches
5 & 6 (Access during Communication Failure).

ON =

Energized:
During a communication failure, the normal state of
the lock output is Energized. When Lock #1 or Lock
#2 is activated, power is removed from the
corresponding lock output to unlock the door.
Activation depends on the setting of the DIP switches
5 & 6 (Access during Communication Failure).

Switch Setting

During a Communication Failure:

5 = off (0)
6 = off (0)

“No Card”
Access is denied to all cards and doors
are locked until communication is restored.

5 = on (1)
6 = off (0)

“2 Cards”
Access is granted only when 2 cards of
a valid format are presented to the reader.

5 = off (0)
6 = on (1)

“All Cards”
Access is granted when any card with
a valid format is presented to the reader.

5 = on (1)
6 = on (1)

“Unlock Door”
Doors are unlocked until communication
is restored.

Address 1 Address 2 Address 3

Doors

Keypad/Reader 1 Door 3

Door 5

Door 7

Keypad/Reader 2 Door 4

Door 6

Door 8

Inputs

Z1

Input 17

Input 21

Input 25

Z2

Input 18

Input 22

Input 26

Z3

Input 19

Input 23

Input 27

Z4

Input 20

Input 24

Input 28

Outputs

OUT1

Output 7

Output 13

Output 19

OUT2

Output 8

Output 14

Output 20

OUT3

Output 9

Output 15

Output 21

OUT4

Output 10

Output 16

Output 22

OUT5

Output 11

Output 17

Output 23

OUT6

Output 12

Output 18

Output 24

Jumpers set to low

Jumpers set to high

A+

B-

LOW

HIGH

LOW

HIGH

A+

B-

Jumper set

as 350mA

Jumper set

as 700mA

Advertising
This manual is related to the following products: