Parameter setting – Panasonic MINAS A3 Series User Manual

Page 24

Advertising
background image

154

Parameter Setting

Parameter

No.

Setting

range

Parameter Name

Unit

Function/Description

Default setting is shown by [ ]

6A

0 – 100

[0]

2ms

Mechanical brake

delay at

motor standstill

The parameter sets time till non-energization of motor (servo free) after

the brake release signal (BRK-OFF) turns off (brake retained), at Serve

Off while the motor stops.

See also “Serve On/Off Operation When the Motor Stops” of the timing

chart of Preparations volume on page 43.

• In order to prevent minor

movement/drop of the motor
(work) due to operation de-
lay time of the brake (tb):

Setting of Pr6A

>

tb.

• See “Serve On/Off Operation

When the Motor Stops” of
the timing chart on page 42.

ON

SRV-ON

BRK-OFF

Actual Brake

Motor Energized

Release

OFF

Retention

Release

Energization

Retention

Non-

energization

Pr6A

tb

=

6B

0 – 100

[0]

2ms

Mechanical brake

delay at

motor in motion

Unlike Pr6A, the parameter sets time till brake release signal (BRK-OFF)

turns off (brake retained) after motor non-energization (servo-free), at Ser-

vo off while the motor is rotating.

See also “Serve On/Off Operation When the Motor Stops” of the timing
chart of Preparations volume on page 42.

• This should be set to prevent de-

terioration of the brake due to
revolutions of the motor.

• At Servo off while the motor is ro-

tating, time tb in the right figure
will be either set time of Pr6B or
time till the motor rotational
speed falls below approximately
30r/min, whichever is smaller.

• See “Serve On/Off Operation When the Motor is

Rotating” of the timing chart of on page 43.

tb

ON

SRV-ON

BRK-OFF

Motor Speed

Release

OFF

Retention

Motor Energized

Energization

Non-

energization

30 r/min

6D

0 – 32767

[35]

2ms

Main power-off

detection time

The parameter sets time to detect shut-off when shut-off of main power

supply continues.

6C

0 – 3

External

regenerative

resister set up

This parameter is set depending on whether to use regeneration resis-
tance built in the driver, or to provide a regeneration resistance in the ex-
ternal (connect between RB1 and RB2 of connector CN X 2 in types A to
D, and between terminal blocks P and B2 in types E - G).

<Request>
When you use an external regeneration, you must install external safe-
guards such as a temperature fuse, etc.
Otherwise, as protection of regeneration resistance would be lost, causing
abnormal heat generation and burnout.
<Caution>
Be careful not to touch an external regeneration resistance.
While you are using an external resistance, it may become hot and scald
you. For type A, only external regeneration resistance is used.

Regeneration

Resistance to Use

Built-in resistance

External resistance

Built-in resistance

External resistance

Protection against Regeneration

Resistance Overload

According to built-in resistance, (about

1% duty) protection against regenera-

tion resistance overload works.

This is activated with operating limits of

the external resistance at 10% duty.

This is activated with operating limits of

the external resistance at 100% duty.

Regeneration resistance does not

work, and a built-in condenser accom-

modates all regenerated power.

Setting

value

[0]

1

2

3