Control of i^2t parameters, Short circuit protection – Parker Products ViX250AE User Manual

Page 37

Advertising
background image

30

VIX AE SERVO DRIVE USER GUIDE

Control of I

2

t Parameters

The drive internal I

2

t parameters are always enabled and cannot be adjusted by the user.

However, the motor I

2

t settings can be influenced by the choice of parameters used for the

MOTOR command. To disable the motor I

2

t settings, set the thermal time constant of the

motor to zero.

Note: If you select a motor from the list of ‘standard motors’ using EASI-V, worst case
configuration data will be used. This prevents reporting a too optimistic view of the motors
thermal performance.

Where a motor is fitted with a temperature sensor built into its windings the motor I

2

t

threshold protection will not be required. In this case, set the thermal time constant of the
motor to zero (see MOTOR command).

Motor Voltage Ratings

Motors with a withstand voltage rating from phase to earth of 1000V AC should be used. An
insulation withstand rating of 500V AC is acceptable if an isolating transformer with earthed
screen is used to power the system, and X1 pin9 (0V/GND) input is earthed, as specified.

Motor Safety Earth/Ground Connection

It is recommended that the motor is independently bonded to a local safety earth point. The
safety earth lead should be at least 2.5mm

2

in area.

Short Circuit Protection

The motor outputs are protected against overload and short circuits. Overload is protected
by the I

2

t circuit, and 300% of continuous drive current rating is only permitted for 2 seconds.

A current level just above rated current is only permitted for a maximum of 20 seconds.

Advertising
This manual is related to the following products: