PVI Industries Durawatt CL User Manual

Durawatt, Cl commercial electric water heater light duty

Advertising
background image

DURAWATT

®

CL

COMMERCIAL ELECTRIC WATER HEATER LIGHT DUTY

Cold Inlet 3/4"
and Drain

Electrical
Connection

H

W

Lower Heating

Element Housing

Upper Heating Element
and Hi-Limit Housing

Temperature and
Pressure Relief Valve

Hot Outlet 3/4"

(extends 1-1/2 inches

from top of tank)

Model Number

Storage

Capacity

KW

GPH Recovery

40º to 120ºF

H

Height

W

Width

Shipping

Weight lbs.

8 C 10-E

10

1.5

8

21

20

110

16 C 10-E

10

3

16

21

20

110

8 C 19-E

19

1.5

8

33

20

151

16 C 19-E

19

3

16

33

20

151

* C 30-E

30

see below

see below

41

20

180

* C 40-E

40

see below

see below

58

20

245

* C 41-E

40

see below

see below

33

26

245

* C 50-E

50

see below

see below

51

22

255

* C 51-E

50

see below

see below

36

28

255

* C 60-E

60

see below

see below

58

22

300

* C 65-E

65

see below

see below

48

26

325

* C 70-E

70

see below

see below

69

22

330

STANDARD EQUIPMENT and FEATURES

• Rotationally molded cement tank lining

• No anode rods required

• Non-ferrous tank fittings

• 150 psi design pressure, 300 psi test pressure

• Relief valve set for 210ºF and 150 psi

(field installed)

• Dual copper-sheathed heating elements with

individual thermostats adjustable to 125ºF *

• Manual-reset high limit control set at 190ºF

• 2" foam insulation

• Composite jacket

• Drain valve

• 5-year non-prorated tank warranty

PVI INDUSTRIES, LLC ▪ FORT WORTH, TEXAS ▪ (800) 784-8326

10 and 19 gallon heaters are not available in 3-phase.

PV 6495 10/07

Voltage Amps per kW

240, 1Ш

4.2

208, 3Ш

2.8

240, 3Ш

2.4

480, 3Ш

1.2

277, 1Ш

3.6

Model Prefix

kW Input

Gph recovery

Number of elements and operation

22 4.5 22

Non-simultaneous

operation of two 4.5 kW elements

30 6 30

Non-simultaneous

operation of two 6 kW elements

44 9 44

Independent

operation of two 4.5 kW elements

60

12

60

Independent operation of two 6 kW elements

*Available prefixes for 30 to 70 gallons models