Omega Speaker Systems DPiTH-i32 User Manual

Omega Speaker Systems Monitors

Advertising
background image

Step 17. Enter Alarm 1 Enable/Disable Submenu
Press

d to display flashing DSBL/ ENBL.

Step 18. Enable Alarm 1 Submenu
If flashing

ENBL is displayed, press a, if DSBL is displayed,

press

b until ENBL is displayed, then press d to store and

go to the next menu item.

Step 19. Select the Deviation Control Type Submenu
Press

d. If flashing _DEV Deviation is displayed press a,

otherwise press

b until flashing _DEV is shown. Now

press

d to store and go to next menu item.

Step 20. Select the Latched Type Submenu
Press

d. If flashing UNLT Unlatched is displayed press a,

otherwise press

b until UNLT is displayed.

Press

d to store and advance to next menu item.

Step 21. Select the Normally Open Type of Contact
Closure Submenu
Press

d. If flashing N.o. Normally Open is displayed,

press

a, otherwise press b until N.o. is displayed. Press d

to store and advance to next menu item.

Step 22. Select the Above Type of Active Submenu
Press

d. If flashing ABoV Above is displayed, press a,

otherwise press

b until ABoV is displayed. Press d to store

and advance to next menu item.

Step 23. Enable Alarm 1 at Power On (

A.P.oN)

Press

d. If flashing ENBL is displayed, press a, otherwise

press

b until ENBL is displayed. Press d to store and

advance to next menu item.

Step 24. Enter Alarm 1 High Submenu
Press

a twice to skip ALR.L Alarm 1 Low value. ALR.L is

for below &

ALR.H for above.

Step 25. Set the Alarm 1 High value (

ALR.H)

Press

d. Press b or c until value to set the display to

002.0. Press d to save.

Step 26. Enter the Alarm 2 Menu
The display will show

ALR2 the top menu for Alarm 2.

Repeat steps from 17 to 25 to set for Alarm 2 the same
conditions as for Alarm 1.

Step 27. Skip the Loop Break Time Menu (

LOOP)

Press

a to go to the OUT1 Output 1 Menu item.

Step 28. Configuration the Output 1 Menu

Set Alarm 1 Disabled (Step 18) to be able to Enable
Output 1.

Step 29. Configuration of Display Color Selection
Press

a until the COLR Display Color Selection Menu

appears on the Display. Configure

COLR as N.CLR / GRN

(green),

1.CLR / RED (red), 2.CLR / AMBR (amber). Please

refer to the operator’s manual if needed.

For color change on Setpoints refer to Owners
Manual Section 2.

OPERATION
Step 1. Apply Power to the Instrument
When your device is first powered up it will display the
ambient temperature (assume 75°F).

Step 2. Enter Setpoint 1 Menu
Press

a one time from run mode to get to SP1 Setpoint 1.

Step 3. Enter the Setpoint 1 Value Submenu
Press

d. Display shows the previous selection of Setpoint 1.

Step 4. Change the Setpoint 1 Value
Press

b or c until desired value is displayed.

Step 5. Store the Setpoint 1 Value
Set the Setpoint 1 to 10 degree higher than Process value
(SP1 = 85) and press

d to store, display flashes STRD

message and advances to

SP2 Setpoint 2 Menu.

Step 6. Store the Setpoint 2 Value
Repeat steps 3 and 4. Set the Setpoint 2 to 5 degree higher
than Process value (SP2 = 80) and press

d to store,

display flashes

STRD message and advances to CNFG

Configuration Menu.

Step 7. Enter the Reading Config Menu
Press

d to enter RDG Reading Config Menu.

Step 8. Enter the submenu items of Rdg Config Menu
Press

d to display SNSR Sensor submenu: Sensor selection

for Autotune, Loop, or Ramp and Soak

°F.°C is for

temperature and

DRRh is for Humidity

Step 9. Enter the submenu items of Rdg Config Menu
Press

d to display Temp Unit submenu:

Step 10 Scroll thru selection for Temp Unit submenu
Press

b to Scroll though the available selections of the

Temperature Unit of your choice:

°F or °C.

Step 11. Store the Temperature Unit
Press

d, display momentarily shows STRD the Unit has

been stored and the instrument will go automatically to the
next menu item.

Step 12. Enter the Filter Constant Submenu
Display shows

FLTR Filter Constant Submenu.

Step 13. Display the Filter Constant Value Submenu
Press

d to display the flashing, previously selected Filter

Constant.

Step 14. Scroll through available Filter Constants
Press

b to sequence thru Filter Constants 0001, 0002,

0004, 0008, 0016, 0032, 0064 and 0128.

Step 15. Store the Filter Constant
Press

d momentarily to store 0004 Filter Constant and the

instrument will automatically go to the next menu item.

Step 16. Enter Alarm 1 Menu
The display will show

ALR1 the top menu for Alarm 1. In the

following steps we are going to enable Alarm 1, Deviation,
Unlatch, Normally Open, Active Above, Enable at power-on
and +2°F High Alarm i.e. Process Value > Setpoint 1 Value
+2°F will activate Alarm 1.

• If Analog Output Option is installed and enabled,

the controller will skip Alarm 1 Menu item to Analog
Output.

• Alarm must be DISABLED if Ramp is ENABLED.
• Alarm1 will only work for Humidity, not

Temperature.

MQS4007/0411

SPECIFICATION

SENSOR SPECIFICATIONS
Relative Humidity Accuracy/Range:
±2% for 10 to 90%
±3% for 5 to 10% and 90 to 95%
±4% for 0 to 5% and 95 to 100%
Non-linearity: ±3%
Hysteresis: ±1% RH
Response Time:
8 sec, tau 63%
Repeatability: ±0.1%
Resolution: 0.1%, 12bit

Temperature Accuracy/Range*:
±0.5°C for 5 to 45°C (±1°F for 41 to 113°F);
up to ±1.5°C for -40 to 5°C and 45 to 124°C
(up to ±2.7°F for -40 to 41°F and 113 to 257°F)

*NOTE: extended temp range is for Probe only, the
Controller’s operating temp is 0-50°C

Response Time:
5 to 30 sec, tau 63%
Repeatability: ±0.1°C
Resolution: 0.1°C, 14 bit
METER SPECIFICATIONS
Display:

4-digit, 9-segment LED,
• 10.2 mm (0.40")

Red, green, and amber programmable
colors for setpoint and temperature units.

Output 1

:

Relay 250 Vac @ 3 A Resistive Load,
SSR, Pulse

Output 2

:

Relay 250 Vac @ 3 A Resistive Load,
SSR, Pulse

Only with -AL Limit Alarm option

Options: Communication

RS-232 / RS-485

or Excitation: 24 Vdc @ 25 mA

Exc. not available for Low Power Option

Line Voltage/Power:

90 - 240 Vac ±10%, 50 - 400 Hz*,

or 110 - 375 Vdc, 4 W

* No CE compliance above 60 Hz

Low Voltage Power Option:

12 - 36 Vdc or 24 Vac** ±10%, 3 W

** Units can be powered safely with 24 Vac

but No Certification for CE/UL are claimed.

Dimensions:

25.4 H x 48 W x 126.3 D mm
(1.0 x 1.89 x 5")

Weight:

127 g (0.28 lb)

Approvals:

CE per EN61010-1:2001

Alarm 1 is designed to monitor the humidity value
around Setpoint 1 and Alarm 2 is designed to monitor
the temperature value around Setpoint 2.

DPiTH-i32 Monitor

CNiTH-i32-AL Limit Alarm

Humidity + Temperature

WARRANTY/DISCLAIMER

OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of
one (1) year from the date of purchase. In addition to OMEGA’s standard warranty period, OMEGA Engineering will
extend the warranty period for four (4) additional years if the warranty card enclosed with each instrument is
returned to OMEGA.

If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will
issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA,
if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply
to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing,
operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit
shows evidence of having been tampered with or shows evidence of having been damaged as a result of excessive
corrosion; or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating
conditions outside of OMEGA’s control. Components which wear are not warranted, including but not limited to
contact points, fuses, and triacs.

OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither
assumes responsibility for any omissions or errors nor assumes liability for any damages that result from
the use of its products in accordance with information provided by OMEGA, either verbal or written. OMEGA
warrants only that the parts manufactured by it will be as specified and free of defects. OMEGA MAKES NO
OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESS OR IMPLIED,
EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION
OF LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of OMEGA with
respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or
otherwise, shall not exceed the purchase price of the component upon which liability is based. In no event
shall OMEGA be liable for consequential, incidental or special damages.

CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic
Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications
or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application,
used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic
WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless
from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.

RETURN REQUESTS/INQUIRIES

Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE
RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR)
NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING
DELAYS). The assigned AR number should then be marked on the outside of the return package and on any
correspondence.

The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in
transit.

FOR WARRANTY RETURNS, please have the
following information available BEFORE
contacting OMEGA:
1.

Purchase Order number under which the product
was PURCHASED,

2.

Model and serial number of the product under
warranty, and

3.

Repair instructions and/or specific problems
relative to the product.

FOR NON-WARRANTY REPAIRS, consult OMEGA for
current repair charges. Have the following information
available BEFORE contacting OMEGA:
1.

Purchase Order number to cover the COST of the
repair,

2.

Model and serial number of product, and

3.

Repair instructions and/or specific problems
relative to the product.

OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords
our customers the latest in technology and engineering.

OMEGA is a registered trademark of OMEGA ENGINEERING, INC.

© Copyright 2011 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied,
reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without
the prior written consent of OMEGA ENGINEERING, INC.

PATENT AND TRADEMARK NOTICE: This product is covered by one or more of the following patents: U.S. Pat.
No. Des. 336,895; 5,274,577; 6,243,021 / CANADA 2052599; 2052600 / ITALY 1249456; 1250938 / GERMANY DE
41 34398 C2 / SPAIN 2039150; 2048066 / UK Patent No. GB2 249 837; GB2 248 954 / FRANCE BREVET NO. 91
12756. The “Meter Bezel Design” is a trademark of Newport Electronics, Inc. USED UNDER LICENSE. Other U.S.
and International Patents pending or applied for.

This device is marked with the international caution symbol. It is important to read the
Setup Guide before installing or commissioning this device, as the guide contains important
information relating to safety and EMC.

WARNING: These products are not designed for use in, and should not be used for, patient-

connected applications.

It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply.
OEMGA is constantly pursuing certification of its products to the European New Approach Directives.
OMEGA will add the CE mark to every appropriate device upon certification.
The information contained in this document is believed to be correct, but OMEGA Engineering, Inc.
accepts no liability for any errors it contains, and reserves the right to alter specifications without notice.
TRADEMARK NOTICE:

®

,

omega.com

®

,

,

and

®

are Trademarks of

OMEGA ENGINEERING, INC.

®

Advertising
This manual is related to the following products: