2-1 overview, 2-2 unit number, Overview – Omron CQM1H-CLK21 User Manual

Page 113: Unit number, Unit no

Advertising
background image

90

CJ-series Controller Link Units

Section 4-2

4-2-1

Overview

Unit Number

Node Address

Baud Rate

Note

Factory default setting is in bold.

Terminating Resistance

4-2-2

Unit Number

Set the unit number for each Unit using the rotary switches on the front of the
Unit. The unit number is used to identify a CPU Bus Unit within the PLC. Any
unit number can be set between 0 and F in hexadecimal (00 to 15 in decimal).

Set the node address using a small flat-blade screwdriver, being careful not to
damage the rotary switches.

Note

1.

Always turn OFF the PLC’s power before setting the unit number.

2.

When setting a Unit for the first time or changing the existing setting, create
a I/O table in the PLC’s CPU Unit.

3.

Do not set the same unit number twice within the same PLC. An error will
occur if the same unit number is set for two different Unit, and the CPU Unit
will not be able to recognize the Units.

4.

When the Unit is recognized by the PLC’s CPU Unit, “NS” will be shown in
the I/O table displayed for the CX-Programmer programming device.

UNIT
No.

RUN

CLK21-V1

ERC

INS

ERH M/A LNK

RD

NODE
No.
x10

1

x10

0

01

23456789

ABCD

EF

0

TER

SD

1 2 3 45

678

9

01

2 3 45

678

9

BAUD
RATE

1
2

ON

SW1

ON

TER SW

BD H

BD L

SHLD

ON

1
2

UNIT
No.

NODE
No.
x10

1

x10

0

01

23456789

ABCD

EF

01

2 3 45

678

9

01

2 3 45

678

9

BAUD
RATE

1
2

ON

SW1

ON

1
2

Setting range

Nodes

01 to F (default is 0)

All nodes in the Network

Setting range

Nodes

01 to 32 (default is 01)

All nodes in the Network

Pins

Baud rate

Maximum

transmission

distance

Nodes

Pin 1

Pin 2

OFF OFF

2 Mbps

500 m

Set same
rate for all
nodes in the
Network.

ON

OFF

1 Mbps

800 m

OFF

ON

500 Kbps

1 km

ON

ON

Cannot be set.

Front switch

Terminating

resistance

Nodes

OFF
(factory default)

Not connected

All nodes in the Network

Turn ON the terminating resis-
tance at the nodes at both
ends of the Network and turn it
OFF at all other nodes.

ON

Connected

Item

Specifications

Setting method

Single-digit hexadecimal

Setting range

0 to F (decimal 00 to 15, default is 0)

Node

All nodes in the Network

UNIT
No.

01

23456789

ABCD

EF

Note: The factory default settings are shown.