5 cqm1h-series controller link units, 5-1 overview, Cqm1h-series controller link units – Omron CQM1H-CLK21 User Manual

Page 123: Overview

Advertising
background image

100

CQM1H-series Controller Link Units

Section 4-5

Note

1.

Always turn OFF the PLC’s power before setting the terminating resistance
switch.

2.

Turn ON the switch to connect terminating resistance at the nodes at both
ends of the Network and turn OFF the switch at all other nodes. Normal
communication cannot be performed in the Network unless all the nodes
are set properly.

3.

The TER indicator will light when the terminating resistance switch is set
to ON.

4-5

CQM1H-series Controller Link Units

The following settings are required for a Controller Link Unit when used with a
CQM1H-series PLC.

4-5-1

Overview

Node Addresses

Setting Baud Rate

Note The factory default setting is in bold.

Terminating Resistance

Item

Switch

Page

Node address

Node address switch

101

Baud rate

Baud rate switch, pins 1 and 2

101

Terminating resistance

Terminating resistance switch

102

Setting range

Nodes

01 to 32 (default is 01)

All nodes in the Network

Switch

Baud rate

Maximum

transmis-

sion dis-

tance

Nodes

Pin 1

Pin 2

OFF

OFF

2 Mbps

500 m

Set same
rate for all
nodes in Net-
work.

ON

OFF

1 Mbps

800 m

OFF

ON

500 Kbps

1 km

ON

ON

Do not set.

Switch

Terminating

resistance

Nodes

OFF
(default)

Not connected

All the nodes

Turn ON the terminating resis-
tance at the nodes at both
ends of the Network and turn it
OFF at all other nodes.

ON

Connected