207

Commands and Responses for Controller Link Units

Section 6-5

Data link data error counter (response): The total number of data link data
reception errors occurring at all nodes is returned as a total count from the
time the power was turned on. It is expressed, in hexadecimal, as one byte
per node. The count can range from 0 to 255 (i.e., 0 to FF in hexadecimal).

When CS1W-CLK21-V1 and CJ1W-CLK21-V1 Units are used and the Wired
Network 62 Node Enable Bit in the DM Parameter Area software switches is
ON, the data link error counter of nodes 33 to 62 is returned in bytes 33
through 62. In other models, the areas corresponding to nodes 33 to 62 are
reserved for system use.

6-5-7

DATA LINK STATUS READ

Reads the data link operational status.

Command Block

Response Block

Note If the type is set to 0000 Hex (or is omitted), only 32 bytes will be returned.

Parameters

Type (Command): The number of nodes reading the data link status is spec-
ified as a 2-byte (4-digit) hexadecimal number as follows:

0000 Hex: 32 nodes
0001 Hex: 62 nodes
Default value: 32 nodes

Reading of the data link status for 62 nodes is enabled only when the Wired
Network 62 Node Enable Bit in the DM Parameter Area software switches of
CS1W-CLK21-V1 and CJ1W-CLK21-V1 Units is ON.

7

6

5

4

3

2

1

0

Bit

Byte 1

Byte 2

Byte 3

Byte 32

Byte 33

Byte 62

Number of error occurrences for node #1

Number of error occurrences for node #2

Number of error occurrences for node #3

Number of error occurrences for node #32

Number of error occurrences for node #33

Number of error occurrences for node #62

Command

code

03

06

Type

Response

code

Command

code

Status flag

Data link mode

Refresh

cycle time

present

value

Refresh

cycle time

maximum

value

Status

06

03

62 bytes
(See note.)