Commands and Responses for C200HX/HG/HE and CQM1H-series PLCs

Section 6-6

No. of bytes (command and response): The command specifies the num-
ber of bytes of data to write. This must be an even number of 07C6 (Hex) or
smaller (1990 or smaller in decimal). The number of bytes actually written will
be returned in the response. The leftmost bit (bit 15) is used to indicate the
completion of the command. It must be turned ON (1) when writing data to the
last address in the program area so that the PLC can generate an index*. To
write only an index marker, specify 8000 (Hex) for the number of bytes.

*Generating an index is a process that enables a program to be used by the
PLC after it has been written. A program will not run properly if the index has
not been generated.

Data (command): The data to be written.

6-6-8

RUN

Changes the PLC to MONITOR or RUN mode, enabling the PLC to execute
its program.

Command Block

Response Block

Parameters

Program no. (command and response): Set to 0000 (Hex).

Mode (command): As follows:

02 (Hex):

MONITOR mode

04 (Hex):

RUN mode

Note If the mode is not specified, the PLC will go to MONITOR mode.

6-6-9

STOP

Changes the PLC to PROGRAM mode, stopping program execution.

Command Block

Bits 0 to 7 (second byte)

Bits 8 to 15 (first byte)

Bit 15 OFF (0): Without last word data
Bit 15 ON (1): With last word data
Bits 0 to 14: No. of bytes written

01

04

00

00

Program

no.

Command

code

Mode

01

04

Response

code

Command

code

Command

code

02

04