3-2 data processing time, Data processing time – Omron CQM1H-CLK21 User Manual

Page 277

Advertising
background image

254

Data Link I/O Response Time

Section 8-3

CVM1 and CV-series PLCs
Under Asynchronous
Operation

When a CVM1 or CV-series CPU Unit is operating in asynchronous mode,
data exchange with the Controller Link Unit is executed as interrupt process-
ing during peripheral processing, regardless of the cycle time of PLC instruc-
tion execution. Data exchange timing is as follows:

More than one data exchange can be executed during a PLC cycle, depend-
ing on the data exchange timing. If interrupt processing for data exchange is
executed, the peripheral servicing interval will be lengthened by the time
required for the interrupt processing (see 8-3-2 Data Processing Time on
page 254).

CS/CJ-series PLCs, CVM1
and CV-series PLCs in
Synchronous Mode,
CQM1H-series PLCs, and
C200HX/HG/HE PLCs

When a CS/CJ-series, CQM1H-series, CVM1, or CV-series PLC is operating
in synchronous mode, a CQM1H-series, or a C200HX/HG/HE PLC is operat-
ing, data exchange with the Controller Link Unit is executed as processing
during peripheral processing for the PLC cycle. Data exchange timing is as
follows:

If processing for data exchange is executed, the PLC cycle time will be length-
ened by the time required for the interrupt processing (see 8-3-2 Data Pro-
cessing Time
bel
ow).

8-3-2

Data Processing Time

The time required to process data exchange (data processing time) can be
roughly estimated as shown in the following table.

The number of words processed in a single data exchange is shown in the fol-
lowing table for each series of PLC. If the number of data link words exceeds
the value shown in the table, data exchange will be executed as several sepa-
rate processes.

Instruction execution

PLC cycle time

Execution

I/O refreshing

PLC processing

Peripheral processing

Peripheral servicing interval

Basic processing

CPU Bus
Unit service

Programming
Device/Host Link
service

Interrupt processing
for data exchange

Execution

Execution

I/O refreshing

I/O refreshing

Interrupt processing
for data exchange

Interrupt processing
for data exchange

Basic processing

CPU Bus
Unit service

Programming
Device/Host Link
service

CPU Bus
Unit service

Programming
Device/Host Link
service

Basic processing

PLC cycle time

Execution

PLC processing

Basic processing

Execution

I/O refreshing

Basic processing

Processing for
data exchange

Peripheral
service

CPU Unit

Equation estimating data processing time

CS1-H, CJ1-H, CJ1M CPU Unit

0.1 ms + Number of transfer words

×

0.7

µ

s

CS1, CJ1 CPU Unit

1.5 ms + Number of transfer words

×

1

µ

s

CVM1-series CPU Unit

1.7 ms + Number of transfer words

×

1

µ

s