1 data links procedures, 1-1 manually setting data links, Data links procedures – Omron CQM1H-CLK21 User Manual

Page 55: Manually setting data links

Advertising
background image

32

Data Links Procedures

Section 2-1

2-1

Data Links Procedures

2-1-1

Manually Setting Data Links

When the data link mode is set for manual data link table creation, the data
link tables can be input using the Controller Link Support Software or CX-Pro-
grammer. Use the following procedure.

1,2,3...

1.

Install and wire the Units.

2.

Prepare for communications.

3.

Turn ON the power to the PLC.

4.

Connect the Programming Device.

5.

Create I/O tables.

Contents

Method

Nodes

Page

a. Mount the Units to

the PLCs.

---

All nodes

59

b. Wire the Network.

---

All nodes

66

Contents

Method

Nodes

Page

a. Set the unit num-

ber.

Use the front rotary
switches.

CS/CJ-series, CVM1,
and CV-series PLCs
only

98

b. Set the node

address.

Use the front rotary
switches.

All nodes

94,98

c. Set the baud rate.

Use the DIP switch.

All nodes

95, 99

d. Set the operating

level.

Use the DIP switch.

C200HX/HG/HE PLCs
only

95

e. Set the terminal

resistance

Use the front switch
for CVM1, CV-series,
CS/CJ-series, and
CQM1H-series PLCs
or the bottom switch
for C200HX/HG/HE
PLCs

.

All nodes

End nodes on the net-
work: ON
All other nodes: OFF

96, 99

Contents

Method

Nodes

Page

Turn ON the power to
the PLC.

---

All nodes

---

Contents

Method

Nodes

Page

Connect the Program-
ming Console or Con-
troller Link Support
Software.

Use the special con-
nection cable.

CS/CJ-series, CVM1,
and CV-series PLCs

21

Contents

Method

Nodes

Page

Input the I/O tables.

Use the Support Soft-
ware or Programming
Console.

CS/CJ-series, CVM1,
and CV-series PLCs
only

---