1-4 cvm1 and cv-series controller link unit, Cvm1 and cv-series controller link unit, Wired unit indicators – Omron CQM1H-CLK21 User Manual

Page 74

Advertising
background image

51

Component Names and Functions

Section 3-1

3-1-4

CVM1 and CV-series Controller Link Unit

Wired Unit Indicators

Unit number switches

Two rotary switches. The unit number is set in 2-digit decimal
for the Network to which the PLC is connected.

Indicators

LED indicators that display the Unit and network status.

Node address switches

Two rotary switches. The node address of the Unit on the
Controller Link Network is set in 2-digit decimal.

Baud rate switch

A four-pin DIP switch. The following setting is made.
Pins 1, 2: Baud rate
Pins 3, 4: Not used (always OFF)

Terminal block for the communications cable

Terminals to connect to the Controller Link Network communications
cable (twisted-pair cable).

Terminating resistance switch

A slide switch. Use this switch to set the terminating resistance to ON for
nodes at both ends of the Controller Link Network.

CLK21

X10

1

X10

0

SW1

ON

BD H

BD L

SHLD

RUN
ERC

TER
ERH

TER SW

1
2
3
4

BAUD
RATE

BAUD RATE

0

0

INS
SD

M/A
LNK
RD

X10

0

NODE
NO.
X10

1

RSV

1

0

BIT2 BIT1

RATE

RSV

OFF
OFF
ON

OFF
ON
OFF

2MBP
1MBP
500KBP

UNIT
NO.
X10

1

(Refer to p. 51 and 287)

(Refer to p. 98)

(Refer to p. 98)

(Refer to p. 99)

(Refer to p. 99)

(Refer to p. 66)

Name

Color

Status

Meaning

RUN
(operating)

Green

Lit

Unit operating normally.

Not lit

Unit error.

TER
(terminating
resistance)

Yellow

Lit

Terminating resistance switch ON.

Not lit

Terminating resistance switch OFF.

ERC (communica-
tions error)

Red

Lit

Communications error, node address
setting error (same address set twice), or
hardware error.

Not lit

Normal operation

ERH
(PLC error)

Red

Lit

PLC error, PLC interface error, EEPROM
error, unit number error, or I/O table not
set

Not lit

No error.

INS
(network
participation)

Yellow

Lit

Unit is participating (inserted) in the net-
work.

Not lit

Unit is not participating (inserted) in the
network.

M/A
(data link mode)

Yellow

Lit

Manual
(see note)

Note:
M/A is always not lit
when data links are not
active in the network.

Not lit

Automatic

LNK
(data link)

Yellow

Lit

Data links participating.

Flashing

Error in data link table.

Not lit

Not in a data link or data link inactive.