APPLICATION GUIDELINE 6.0

* For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-2192

REMOTE MOUNT EOI

Electronic Operator Interface

Introduction

This G7 Electronic Operator Interface (EOI) can be mounted remotely from the unit. This guideline
provides the information for mounting the EOI properly to avoid damage to your interface. The
mounting screw length is most critical in remote mounting the EOI. You may cause deformation of
the outer surface of the bezel if the screws used are too long. The interface can operate safely up to
distances of 15 feet via the TTL Port. For distances beyond 15 feet, it is recommended to use the
RS-485 Port.

EOI

Mounting dimensions (in.)

Mounting Instructions

Parts Required
• 6-32 x 5/16 Long Pan Screw (Qty. 4 each)
• #6 Split Lock Washer (Qty. 4 each)
• #6 Flat Washer (Qty. 4 each)
• 1 of the following cables
CAB0011-0 (1 meter option connection cable)
CAB0013-0 (3 meter option connection cable)
CAB0015-0 (5 meter option connection cable)