I/o signal list, One station is occupied (cc-link ver.1) (c122=0) – Toshiba TOSVERT VF-S15 series option unit Function E6581830 User Manual

Page 18

Advertising
background image

E658130

- 17 -

5.5.

I/O signal list

5.5.1. One station is occupied (CC-Link Ver.1) (c122=0)

This option occupies one station area of the buffer memory of the PLC.
In the case of c122 = 0, there are remote I/O (RX, RY both 32 bits) and the remote register
(RWw, RWr both 4 word) in the communication data for one station area.

Remote I/O

(Default value

= 0)

Inverter (Slave) → PLC (Master)

PLC (Master) → Inverter (Slave)

Device No.

Signal

Device No.

Signal

RXn0

Forward running

RYn0

Forward rotation command

RXn1 Reverse

running

RYn1 Reverse

rotation

command

RXn2

Output terminal 1 (RY-RC)

RYn2

Input terminal 3 (S1)

RXn3

Output terminal 2 (OUT)

RYn3

Input terminal 4 (S2)

RXn4

Output terminal 3 (FL)

RYn4

Input terminal 5 (S3)

RXn5

Failure FL

RYn5

Input terminal 6 (S4)

RXn6

PI control OFF

RYn6

Input terminal 7 (PIOFF)

RXn7

Acceleration/deceleration
pattern selection (1 or 2)

RYn7

Input terminal 8 (AD1)

RXn8

Emergency stop

RYn8

Input terminal 9 (ESTP)

RXn9

Coast stop (ST = OFF)

RYn9

Intercept output to inverter
(Coast stop)

RXnA Alarm

RYnA Frequency

priority

CC-Link

RXnB Reserved*

RYnB Command

priority

CC-Link

RXnC Monitoring

RYnC Monitor

command

RXnD

Frequency setting completion
(RAM)

RYnD

Frequency setting command
(RAM)

RXnE Reserved*

RYnE Reserved**

RXnF

Instruction code execution
completion

RYnF

Instruction code execution request

RX(n+1)0

to

RX(n+1)9

Reserved*

RY(n+1)0

to

RY(n+1)9

Reserved**

RX(n+1)A Error

status

flag

RY(n+1)A

Error reset request flag
(A reset request is during switched
ON)

RX(n+1)B

Remote station ready

RY(n+1)B

Reserved**

RX(n+1)C

to

RX(n+1)F

Reserved*

RY(n+1)C

to

RY(n+1)F

Reserved**

"n" is depend on the station number.

* The bit described "

Reserved

" is unstable. Don't use the “

Reserved

" bit for the judgment.

** Set OFF (“0”) to reserved bit.

Remote register (Default value

= 0)

RWr Inverter → PLC

RWw PLC → Inverter

Address Signal Address Signal

RWr n

Monitor value 1

RWw n

Monitor code (1 and 2)

RWr n+1

Monitor value 2
(output frequency)

RWw n+1

Set frequency

RWr n+2

Reply code

RWw n+2

Instruction code

RWr n+3

Read data

RWw n+3

Write data

"n" is depend on the station number.