5.5.7. Remote Register Assignment

Divide the monitor code (RWw n) into half and select the monitor value 1 (RWr n) from the
lower 8 bits and the monitor value 2 (RWr n) from the higher 8 bits.
For example: When output voltage is selected for the monitor value 1 and output torque is
selected for the monitor value 2. -> The monitor code is 0703H.
* The hexadecimal value attaches and expresses "H" to the end of a number.

1. Remote register (Master -> inverter)

RWw

Address Signal

Description

RWw n

Monitor code

(1 and 2)

Set the monitor code to be referenced. By switching on the (RYnC) signal
after setting, the specified monitored data is set to (RWr n).
The monitor value 1 (RWr n): RWw n Setting of the lower 8 bits of monitor
code.
The monitor value 2 (RWr n+1): RWw n Setting of the upper 8 bits of
monitor code.

RWwn+1 Set

frequency

Set the set frequency. After setting the register, a frequency is written

after turning on (RynD). When the writing of the frequency is completed,
(RXnD) turns on, depending on the input command.

Unit: 0.01Hz

RWwn+2

Command code 1

Set the command code for actions such as operation mode switching,
parameter read, write, error reference, error clear, etc. The command will
be executed by turning (RynF) on after the register setting is completed.

When the command execution is completed, (RXnF) turns on.

RWwn+3

Write data 1

Set data specified by the above-mentioned command code
(if necessary).
If no data needs to be written, the value shall be zero.
(RynF) is turned on after setting the above-mentioned command code

and this register.

RWwn+4

Monitor code 3

Set the monitor code to be monitored. By setting "ON” in (RYC) after

setting, the specified monitored data is stored in RWr n+4.

RWwn+5

Monitor code 4

Set the monitor code to be monitored. By setting "ON” in (RYC) after

setting, the specified monitored data is stored in RWr n+5.

RWwn+6

Monitor code 5

Set the monitor code to be monitored. By setting "ON” in (RYC) after

setting, the specified monitored data is stored in RWr n+6.

RWwn+7

Monitor code 6

Set the monitor code to be monitored. By setting "ON” in (RYC) after

setting, the specified monitored data is stored in RWr n+7.

RWwn+8 Trip

history

No.

Set how many fault records in past to be read.
Upper 8 bits: H00 (latest fault) to H07 (eight faults in past)
Lower 8 bits: H00

RWwn+9

to

RWwn+F

Reserved

Reserved