E658130

- 28 -

5.5.8. Instruction Codes

Code No.

Item

Description

1003H

Command mode selection
read

2003H

Command mode selection
write

0: Terminal block
1: Panel keypad (including extension panel)
2: RS485 communication
3: No function
4: Communication option

1004H

Frequency setting mode
selection read

2004H

Frequency setting mode
selection write

0: Setting dial 1(save even if power is off)
1: Terminal VIA
2: Terminal VIB
3: Setting dial 2(press in center to save)
4: RS485 communication
5: UP/DOWN from external logic input
6: No function
7: Communication option
8: Terminal VIC
9, 10: -
11: Pulse train input
12, 13: -
14: sro

0072H Special

monitor

0000H to FFFFH:
Monitor value selected after choosing instruction code 00F3H.

read 0073H Special monitor code read

Read the content that was monitored by special monitor.

write 00F3H Special monitor selection

Select the monitor code of special monitor.

0074H

Trip history No.1, No.2 read

Read the No.1 and No.2 of trip information.

0075H

Trip history No.3, No.4 read

Read the No.3 and No.4 of trip information.

0076H

Trip history No.5, No.6 read

Read the No.5 and No.6 of trip information.

0077H

Trip history No.7, No.8 read

Read the No.7 and No.8 of trip information.

006DH

Frequency command value
(RAM) read

Read the frequency command value (RAM).

00EDH

Option frequency command
value (EEPROM&RAM) write*

Write the option frequency command value (EEPROM &RAM).

00F4H

Trip history clear

9696H: Clear all trip histories.

00FCH

Parameter all clear

9696H: Clear all parameters. (Parameters other than
proofreading values are made into factory default settings.)

00FDH

Inverter reset

9696H: Reset the inverter.

1000H to 1999H

(1000H to

1F99H)

Read parameters (RAM)

To read parameters f000 to f984, add the triple figures
that follow Fxxx to 1000H.

(Ex: f984 -> 984 + 1000 = 1984)

No error occurs when you select 1A00 to 1F99.
Because these parameters are for maintenance.

2000H to 2999H

Write parameters
(EEPROM&RAM) *

To write parameters f000 to f984, add the triple figures
that follow Fxxx to 2000H.