Program example for setting the operation commands, Program example for setting the running frequency – Toshiba TOSVERT VF-S15 series option unit Function E6581830 User Manual

Page 41

Advertising
background image

E658130

- 40 -

6.3.

Program example for setting the operation commands

Example 3 shows

a ladder logic to

give a forward command to station 2 inverter.











6.4.

Program example for setting the running frequency

Example 4 shows

a ladder logic to

chang the running frequency of station 1 inverter to

50.00Hz
Set frequency: 5000 (decimal)


























X0

X0F

X1

SW80.1

M0

X20

( M0)

(Y1020)

Check the ready of the Station 2

Forward rotation command (RY20)

Example 3

X100D

M302

X0

X0F X1

( M0)

SW80.0

M0

X20

[ PLS M300]

M300

[ SET M301]

M301

X100D

[ MOV K5000 W101]

[ SET Y100D]

[ RST Y100D]

[ RST M302]

[ END]

[ RST M301]

[ SET M302]

Check the ready of the station 1

Write set frequency to

Turn off the frequency setting
command RAM (RY0D)

Turn off instruction frequency writing
(RY0D), when instruction frequency
writing completion flag (RX0D) is
turned on.

Example