4.3. Connection of CC-Link master unit and inverter

The example of the connection of the CC-Link master unit and the inverter is shown.。

CC-Link

Master

Unit

DA

DB

DG

SLD

FG

CCL003Z

DA

DB

DG

SLD

FG


Inverter

VF-S15

R/L1

S/L2

T/L3

U/T1

V/T2

W/T3

I M

Motor

*Connection of Several Inverters

Factory Automation can be applied to several inverters which share a link system as

CC-Link remote device stations and are controlled and monitored by PLC user programs.

DA,DB

Shield twisted cable

DG

SLD / FG

Connect the shielded wire of the dedicated CC-Link cable to the “SLD” of each

module, and ground both ends of the shielded wire using type-D grounding (class 3

grounding) via “FG.”

(

The ground resistance is 100Ω or less.)

Terminal resistor

Connect the terminal resistor of 110Ω.

(130Ω is a resistance value for the CC-Link Ver.1.00 dedicated high performance cable.)

DA

DB

DG

SLD

FG

DA

DB

DG

SLD

FG

Mater unit

Inverter

Shield twisted cable

Shield twisted cable

Terminal

resistor

DA

DB

DG

SLD

FG

Inverter

Terminal

resistor

110Ω 1/2W

(130Ω 1/2W)

110Ω 1/2W

(130Ω 1/2W)