Honeywell T8511G User Manual

Microelectronic heat pump thermostats, T8511g, Mercury notice

Advertising
background image

X-XX UL

INSTALLATION INSTRUCTIONS

®U.S. Registered Trademark • • All Rights Reserved

Microelectronic

Heat Pump Thermostats

T8511G

APPLICATION

The T8511G Microelectronic Heat Pump Thermostat provides electronic control of 24 Vac, two-stage heating and one-
stage cooling heat pump systems. Refer to Table 1 for a general description of the thermostat. All T8511 Thermostats
require a common wire to supply power.

Table 1. T8511 Thermostat Desription.

MERCURY NOTICE

If this control is replacing a control that contains
mercury in a sealed tube, do

not

place your old

control in the trash.

Contact your local waste management authority for
instructions regarding recycling and the proper
disposal of the old thermostat.

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow

the instructions can damage the product or cause a
hazardous condition.

2. Check the ratings given in the instructions and on

the product to make sure the product is suitable for
your application.

3. Installer must be a trained, experienced service

technician.

4. After completing installation, use these instructions

to check out the product operation.

CAUTION

Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.

Location

Install the thermostat about 5 ft (1.5m) above the floor in
an area with good air circulation at average temperature.
See Fig. 1.

Do not install the thermostat where it can be affected by:

drafts, or dead spots behind doors and in corners.

hot or cold air from ducts.

radiant heat from sun or appliances.

concealed pipes and chimneys.

unheated (uncooled) areas such as an outside wall
behind the thermostat.

Wallplate Installation

Mount tthermostat horizontally on the wall or on a 2 in. x 4
in. wiring box.

1. Position and level the wallplate (for appearance

only). The thermostat functions properly even when
not level.

T8511

Changeover

System Selection

Fan

Selection

Comments

G

Automatic

Em. Heat-Heat-Off-Auto-Cool

On-Auto

Use keyboard to make system and
fan selections.

69-0961-4