OPERATION

Wiring

All wiring must conform to local and national electrical codes and ordinances.

Connect in accordance with the wiring diagrams provided by the equipment manufacturer. If none are
provided, the following represents a typical installation.

Limit

Switch

Fan

Switch

Fan

Motor

Optional Remote

Manual Switch

For Summer Fan

Jumper

Factory Installed

On Some Models

To Oil Burner

Control Or

Transformer Primary

Diagram Using Limit In Line Voltage Circuit

L1

Line

L2

Note:Make L1 “HOT” on

120V installation

Limit

Switch

Fan

Switch

Fan

Motor

Optional Remote

Manual Switch

For Summer Fan

To Low Voltage

Or Millivolt

Burner Circuit

Diagram Using Limit In Low Voltage

or Millivolt Circuit

L1

Line

L2

Note:Make L1 “HOT” on

120V installation

CAUTION: Line voltage jumper is factory installed on

some models. This jumper must be removed
when limit switch is used in low voltage or
millivolt circuit.

SUMMER FAN OPERATION

The cover does not have to be removed to access the
lever. To turn the fan on, slide the lever to the left “MAN”
position. To turn the fan off, slide the lever to the right
“AUTO” position.

For automatic operation of the fan during the heating or
cooling season, the lever must be in the “AUTO” position.

SETTING THE DIAL

To set pointers, hold dial securely with one hand and
move the pointers with the other hand. Do not force the
pointers past any stops on the dial even though the dial
may be graduated beyond the stops.

Limit

Move the right hand pointer so that its straight edge
indicates the temperature at which the contacts should
open. The limit pointer should never be set any higher
than the setting recommended by the furnace manufac-
turer.

Fan

Move the “Fan On” pointer so that its straight edge
indicates the temperature at which the fan contacts should
close to start the blower. Move the “Fan Off” pointer so that
its straight edge indicates the temperature at which the
fan contacts should open to stop the blower.

5

0

10

0

15

0 200 250

30

0

FAN

LIMIT

HOLD DIAL WHEN

CHANGING INDICATORS

DO NOT ADJUST

SAFETY STOP

Left Hand

Pointer

(Fan Off)

Center

Pointer

(Fan On)

Right Hand

Pointer

(Limit Opens)

Limit Stop

MAN

AU

TO

Advertising