Specifications, Specifications, 34, Specific specifications – Watlow Series 733 Service User Manual

Page 34

Advertising
background image

Appendix

34

WATLOW Series 733/734 Service Manual

Specific

Specifications

Control Mode
• Single or dual input, single or dual output, single alarm.
• EIA/TIA-422A, EIA/TIA-423A, or EIA/TIA-485 data

communications.

• ON/OFF: Determined by the HYSX parameter for

Outputs 1 and 2.

• PID Parameters:

• Proportional band: 0 to 999°F/0 to 555°C/0 to 999
units.
• Reset: 0.00 to 9.99 repeats per minute.
• Rate: 0.00 to 9.99 minutes.
• Cycle time: 1 to 60 seconds.

Operator Interface
• Membrane front panel.
• Single, four-digit 0.56" (14 mm) LED displays.
• TIME, TEMPERATURE, UP/DOWN & 1-12 menu
keys.
Input
• Thermocouple, RTD and electrical process input.
• Automatic cold junction compensation for thermocouple.
• RTD input, 2- or 3-wire, platinum, 100 @ 0°C, solfware

selectable: JIS curve #3916 (0.003916 / °C) or DIN
curve #3850 (0.003850 / /°C).

• Sensor break protection de-energizes control outputs to

protect system.

• Grounded or ungrounded sensors. (Dual input requires

at least one ungrounded t/c. See Chapter 1 of the
Series 733/734 Service Manual.
)

• °F, °C or process variable units are user selectable.
• Operating ranges user selectable.

J t/c:

32 to

1382°F

or

0 to

750°C

K t/c:

32 to

2282°F

or

0 to

1250°C

E t/c:

32 to

1220°F

or

0 to

660°C

RTD:

32 to

1112°F

or

0 to

600°C

Process: -500 to

3500 units

Primary Output (Zone 1)
• Solid-state Relay, Form A, 0.4A @ 120/208/240V

Å

(VAC), 30VA pilot duty @ 120/208/240V

Å

(VAC), opto-

isolated, zero-cross switching. Off state impedance is
20K minimum with contact suppression, 31M without
contact suppression.

• Electromechanical Relay, Form A, 1A @ 24/120/208/

240V

Å

(VAC), 1/8 hp. @ 120/240V

Å

(VAC), 125VA pilot

duty @ 24/120/208/240V

Å

(VAC). Off state impedance is

20K minimum. 200m contact resistance, maximum.

• Switched DC, 500 minimum load resistance, 1K load,

9mA minimum, 22mA maximum, non-isolated.

• 0-20mA/4-20mA reverse or direct into a 600 maximum

load impedance, non-isolated.

• 0-5V

Î

(VDC)/0-10V

Î

(VDC) reverse or direct into a

10K minimum load impedance, non-isolated.

Secondary Output (Zone 2)
• Solid-state Relay, Form A, 0.4A @ 120/208/240V

Å

(VAC), 30VA pilot duty @ 120/208/240V

Å

(VAC),

opto-isolated, zero-cross switching. Off state imped-
ance is 20K minimum with contact suppression,
31M without contact suppression.

• Electromechanical Relay, Form A, 1A @ 24/120/208/

240V

Å

(VAC), 1/8 hp. @ 120/240V

Å

(VAC), 125VA

pilot duty @ 24/120/208/240V

Å

(VAC). Off state

impedance is 20K minimum. 200m contact
resistance, maximum.

• Switched DC, 500 minimum load resistance, 1K

load, 9mA minimum, 22mA maximum, non-isolated.

• 0-20mA/4-20mA reverse or direct into a 600 maximum

load impedance, non-isolated.

• 0-5V

Î

(VDC)/0-10V

Î

(VDC) reverse or direct into a

10K minimum load impedance, non-isolated.

Alarms
• Electromechanical Relay, Form A, 1A @ 24/120/208/

240V

Å

(VAC), 1/8 hp. @ 120/240V

Å

(VAC), 125VA

pilot duty @ 24/120/208/240V

Å

(VAC). Off state

impedance is 20K minimum. 200m contact resis-
tance, maximum.

• Latching or non-latching.
• Process or deviation.
• Separate high and low values.
• Alarm silencing (inhibit) on power up for alarm.
Event Outputs
• Switched DC, non-isolated, 5V

Î

(VDC), 5mA maximum.

Accuracy
• Calibration Accuracy & Sensor Conformity: ± 0.1% of

span, ± 1LSD, 77°F ± 5°F(25°C ±3°C) minimum.

• Accuracy Span: Normally 1000° minimum span.
• Temperature Stability: < 0.2°F/°F (0.2°C/°C) change

in ambient.

• Voltage Stability: ± 0.01% of span / % of rated line

voltage.

Communications
• Serial data communications.
• EIA/TIA-422A or EIA/TIA-423A (EIA/TIA-232C

compatible) or EIA/TIA-485.

• ANSI X3.28 protocol, or XON/XOFF protocol.
• Isolated.
Agency Approvals
• UL® 873, File #E43684.
• CSA Certified, File #LR30586, C22.2.
• Select models CE approved. Consult factory for details.

Electronic Incorporated Class III Control, Type 2 action.

Connectors
• Compression type screw terminals and universal

Mate-n-Lok.

Power
• 24V

Å

(VAC) +10%, - 15%.

• 50 to 60 Hz ± 3%.
• Consumption 6 - 10VA.
• For CE-approved models, input power limited to 15

watts maximum. All components are rated for a
maximum of 15 watts.

Operating Environment
• 32 to 176°F/0 to 80°C.
• 0 to 90% RH, non-condensing.
Dimensions
733A-xxxx-xxxx (horizontal) models:
• Height:

3.28"

83 mm

• Width:

10.66"

271 mm

• Depth:

2.00"

51 mm

734A-xxxx-xxxx (vertical) models:
• Height:

10.66"

271 mm

• Width:

3.28"

83 mm

• Depth:

2.00"

51 mm