Table 37: 6 point load weight, Table 38: unit weight, Figure 5 - unit dimensions – York PREDATOR DM 078 User Manual

Page 36: Table 39: unit height, Table 40: unit clearances, Detail a table 40: unit clearances

Advertising
background image

246645-YTG-C-0708

36

Johnson Controls Unitary Products

TABLE 37: 6 POINT LOAD WEIGHT

Model

Locations (lbs.)

A

B

C

D

E

F

DM078

156

140

127

185

205

228

DM090

135

110

91

142

172

211

DM102

137

112

93

145

145

214

DM120

168

151

136

198

219

244

DM150

180

161

145

212

235

262

TABLE 38: UNIT WEIGHT

Model

Shipping Weight (lbs.)

Operating Weight (lbs.)

DM078

1046

1041

DM090

865

860

DM102

880

875

DM120

1121

1116

DM150

1200

1195

FIGURE 5 -

UNIT DIMENSIONS

See Detail
A

For Baserail
Dimensions
See Detail B

89

27

59

4-1/4

6-3/16

17-3/16

24-3/16

30-3/16

Convenience

Power
Outlet

Entry
Ø 7/8

Power

Entry

Ø 2-1/2

30-11/32

Control

Entry
Ø 7/8

Power

Entry

Ø 2-1/2

LEFT

FRONT

For Drain
Dimensions
See Detail C

11-1/2

X

TABLE 39: UNIT HEIGHT

Unit Model Number

X

DM078

50 3/4

DM090

42

DM102

42

DM120

50 3/4

DM150

50 3/4

5 - 1 / 4

B a s e

P a n

1 7 - 1 3 / 1 6

V i e w o f W a l l A c r o s s f r o m C o i l

G a s P i p e I n l e t

DETAIL A

TABLE 40: UNIT CLEARANCES

Top

*

*

Units must be installed outdoors. Overhanging struc-
ture or shrubs should not obstruct condenser air dis-
charge outlet.

72”

Right

12”

Front

36”

Left

36”

Rear

To remove the slide-out drain pan, a rear clearance of
60” is required. If space is unavailable, the drain pan
can be removed through the front by separating the
corner wall.

36”

Bottom

Units may be installed on combustible floors made from
wood or class A, B or C roof covering materials.

0”

Advertising