Installation

MCS5, MCS15

16

8.1

Spacing Allowances and Unit Dimensions

Key to fig. 2, page 3:

I

NOTE
The blower and duct ring can be positioned either vertically or
horizontally; fig. 2, page 3 shows a Marine Climate System MCS5 with
blower rotated to vertical position.

Space allowances (fig. 2, page 3)

The following space allowances should be considered when mounting
the unit:

Allow a minimum of 152 mm around the perimeter of the unit in the
area of the seawater and condensate drain piping (1).

Allow a minimum of 76 mm of air space in front of the evaporator coil
for the return-air intake if it is adjacent to a bulkhead (2).

For flexible ducting connection (10) and for clearance needed behind
the supply-air grille
– allow 51 mm for the duct ring,
– allow 25 mm for the duct bend radius and
– add diameter of the ducting to get the total clearance distance.

Allocate enough space for installation and serviceability.

Item

Description

1

Space allowance for return-air intake
(if adjacent to bulkhead)

2

Space allowance for seawater piping

3

Evaporator and condenser coil

4

Duct ring

5

Electric box

6

Rotary compressor

7

Refrigent connection
(allow space for access)

8

Seawater in

9

Seawater out

10

Total minimum clearance

11

Standard blower position as shipped

12

Possible drain position