Installation

Unit dimensions (fig. 2, page 3)

I: Top view

II: Side view

III: Back view

8.2

Condensate Drains

!

WARNING!
Do not terminate condensate drain line

– within 0.9 m of any outlet of engine or generator exhaust systems,
– in a compartment housing of an engine or generator,
– in a bilge, unless the drain is connected properly to a sealed

condensate or shower sump pump.

Failure to comply may allow bilge or engine room vapors to mix with the
air conditioners return-air and contaminate living areas which may result
in injury or death.

The following guidelines should be followed during the installation of the
condensate drains:

Do not route condensate drains to the bilge.

Run the condensate drain line downward from the unit to a suitable
drain location.

The condensate drain line should have a trap.

For installation of the condensate drain (fig. 3, page 4):

➤ Remove the aft facing watertight plug from the base pan (4) of the air

conditioning unit.

➤ Slip the solid washer (2) and the liquid-seal washer (3) onto the PVC

fitting (1) in that order.

➤ Connect the PVC fitting (1) through the exposed hole in the base

pan (4) with the locking nut (5).

➤ Securely tighten with two wrenches to provide a proper seal.

Unit Capacity

MCS5

MCS15

mm

mm

A – Duct Size

102

153

B – Base Depth

204

254

C – Overall Depth

229

268

D – Width

407

559

E – Height

286

343