Installation

MCS5, MCS15

18

➤ Attach a 5/8

"

(16 mm) I.D. reinforced hose to the hose barb and

secure with stainless steel hose clamps.

➤ Install the condensate drain hose downhill from the unit and aft to a

sump.
The hose should have a trap.

I

NOTE

Two drain fittings may be used and the hoses teed together provided
there is a minimum 51 mm drop from the bottom of the base pan to the
tee connection.

Consideration should be given to installing a trap in the condensate
drain line(s) so that normal discharge of condensate can fill the trap
and prevent the ingress of carbon monoxide (CO) or other potentially
harmful vapors.

➤ Test the installation by pouring one liter of water into the pan and

checking for good flow.

8.3

Blower Assembly

Horizontal or vertical supply-air discharge may be achieved by rotating
the blower (fig. 4 1, page 4). Rotate the blower to allow the most direct
flow of air to the supply-air grille

8.3.1

MCS5

➤ Remove wire tie holding blower wire harness to base pan and/or

adjacent harness.

➤ Remove and save the 7 screws (fig. 4 5, page 4) holding the blower

plate to the evaporator shroud.

➤ Rotate the blower 90° so the discharge is in the vertical position and

aimed upward.

➤ Reinstall the 7 screws to hold the blower plate to the evaporator

shroud.

➤ Make sure the power wire is repositioned so it will not catch on any-

thing during or after installation.

✓ The vertical rotation is complete.