EN

Installation

MCS5, MCS15

20

Mount the electrical box within 4.5 m of the location where the digital
control will be installed.

➤ Use the 3 keyhole mounting slots in the back of the electric box to at-

tach it to a suitable mounting surface.

➤ Use screws appropriate for that mounting surface (not included).

8.5

Supply-Air Grille

The following guidelines should be followed during the installation of the
supply-air grille to ensure direct uninterrupted airflow to the evaporator:

A

NOTICE!
In no instance should the supply-air grille discharge be directed towards
the return-air grille, as this will cause the system to short cycle.

Install the supply-air grille as high as possible.

A minimum clearance of 76 mm plus the duct diameter size (fig. 6 3,
page 6) is required behind the supply-air grille for attaching the duct-
ing (fig. 2 11, page 3).

➤ Create the cut outs for the round supply-air grille according to the

following table:

➤ Mount the supply-air grille.

8.6

Return-air Grille

The following guidelines should be followed during the installation of the
return-air grille to ensure direct uninterrupted airflow to the evaporator:

Install the return-air grille as low and as close to the unit as possible.

Install the return-air grille away from exhaust and bilge vapors.

The return-air grille should have a minimum of 107 mm of clearance
in front of it in the cabin area.

➤ Create the cut out for the return-air grilles according to the following

table:

MCS5

MCS15

4,4 x 4,4"

112 x 112 mm

9.6 x 7.6"

254 x 204 mm

MCS5

MCS15

9.6 x 7.6"

244 x 194 mm

13.6 x 9.6"

346 x 244 mm