Functional Description

The FPP-5000-TI is an extension for the FPP-5000 External Power Supply Unit Kit 24 V/6 A.
It provides the fault message transfer of the mains fault signal and the battery fault signal to
the fire panel via the Local SecurityNetwork LSN. The two fault messages are provided by the
corresponding outputs at the BCM-0000-B Battery Controller Module. The FPP-5000-TI is
directly connected to the LSN data bus and is also power supplied via the LSN data bus line.

Terminal Assignment

Technical Specifications

Pos.

Labelling

Connection

1

AUX1 -

Auxiliary power supply incoming
(support points to loop through)

2

AUX1 +

3

LSN1 a1 -

LSN incoming

4

LSN1 b1 +

5

SHIELD

Shield wire

6

SHIELD

7

AUX2 -

Auxiliary power supply outgoing
(support points to loop through)

8

AUX2 +

9

LSN1 a2 -

LSN outgoing

10

LSN1 b2 +

11

AC FAULT -

Mains fault input

12

AC FAULT +

13

BATT FAULT -

Battery fault input

14

BATT FAULT +

FPP-5000-TI Trouble Interface for FPP-5000

Input voltage (min - max)

+15 V DC. . . +33 V DC

Maximum current consumption

1.15 mA at 24 V DC (from LSN)

Protection type as per IEC 60529 IP 20

Permissible operating temp.

-5 °C . . . 50 °C (23 °F . . . 122 °F)

Permissible storage temp.

-20 °C . . . 60 °C (-4 °F . . . 140 °F)

Relative humidity

Max. 95 % non-condensing

Address setting

Via eight DIP switches

Housing material and color

ABS plastic, (UL94 V-0), semi-gloss anthracite, RAL 7016

Dimensions (W x H x L)

Approx. 127 x 96 x 60 mm (approx. 5.0 x 3.8 x 2.4 inches)