Power Supply Wiring

The 340 BN/MB Btu Energy Transmitter requires 12-24 Volts AC or DC to operate The power connections are made to the

ORANGE header The connections are labeled beside the header Observe the polarity shown on the label
If a Badger Meter plug-in type power supply (Series A-1026 or A-503) is used, connect the black/white striped wire to the

terminal marked positive (+) and the black wire to the terminal marked negative (–)

Comm LED

Data

Industrial

Shield

Signal

Signal +

Power Out

-

RE

F

+

_

D.

I.C.

Co

mm

Po

rt

+

-

Po

wer In

AC C /DC

AC L /DC

Output LED

Output

Pulse Out +

Pulse Out -

1

2

3

Temp
1

1

3

Temp
2

2

Input LED

DC +

or

AC Load

DC -

or

AC Common

Earth

Ground

AC or DC

Power Supply

Sensor Inpu

t

Model: 340

S/N 340-

XXXXXX

Figure 8: Sample Power Supply Wiring

NOTE:

N

Included with every 340 BN/MB Btu Energy Transmitter is a 340IK kit containing a screw, lock washer and nut to

connect the transmitter to earth ground Connect the earth ground lug of the 340 BN/MB Btu Energy Transmitter to

a solid earth ground with as short a wire as possible This will help prevent electrical interference from affecting the

transmitter’s normal operation

Installation & Operation Manual