SPECIFICATIONS

Thermostat Power Requirements

19-30VAC; 50 or 60 Hz; 2 VA Class 2

Operating Conditions

0° to 50°C (32° to 122°F); 0 to 95% RH non-condensing

Storage Conditions

-30° to 50°C (-22° to 122°F); 0 to 95% RH non-condensing

Temperature Sensor

Local 10 K NTC thermistor

Resolution

± 0.1°C (± 0.2°F)

Control Accuracy

Temp: ±0.5°C (±0.9°F ) @ 21°C (70°F) typical, calibrated

Occupied and Unoccupied Setpoint Range Cooling

12° to 38°C (54° to 100°F)

Occupied and Unoccupied Setpoint Range Heating

4.5° to 32°C (40° to 90°F)

Room and Outdoor Air Temperature Display

-40° to 50°C (-40° to 122°F)

Proportional Band for Room Temperature Range Control

Cooling & Heating: 1.8°C (3.2°F )

Binary Inputs

Dry contact across terminal BI1, BI2 & UI3 to Scom

Outputs Rating

Triac output: 30VAC, 1A max., 3A in-rush; Analog: 0 to 10VDC into 2kΩ resistance min.

Economizer Analog Output Rating

0 to 10VDC into 2kΩ resistance min.

Economizer Analog Output Accuracy

±3% typical

Wire Gauge

18 gauge maximum, 22 gauge recommended

Dimensions

4.94” x 3.38” x 1.13”

Approximate Shipping Weight

0.75 lb (0.34 kg)

UL: 873 (US) and CSA C22.2 No. 24 (Canada), File E27734 with CCN , XAPX (US) and XAPX7 (Canada)

FCC: Compliant to CFR 47, Part 15, Subpart B, Class A (US)

Industry Canada: ICES-003 (Canada)

CE: EMC Directive 89/336/EEC (European Union)

C-Tick: AS/NZS CISPR 22 Compliant (Australia / New Zealand); Supplier Code Number N10696

DESCRIPTION

The VT7600H PI thermostat family is designed for multi-stage control of heating/

cooling equipment such as heat pumps and self-contained units. The product

features an intuitive, menu-driven, back-lit LCD display which walks users through

the programming steps, making the process extremely simple.

All models contain two user-controlled digital inputs that monitor filter status,

change the occupancy status, and/or provide general purpose service indication.

Some models include up to three remote sensor inputs. All devices are available with

Echelon, BACnet, or wireless adapters.

APPLICATIONS

Single speed fans

Supply air temperature sensor

Outdoor air temperature sensor

Differential pressure switch

FEATURES

PI time proportioning algorithm...increased comfort, accuracy,

and energy savings

Smart fan...saves energy during night mode

Unique local configuration utility...minimizes parameter tampering

Lockable keypad...tamper proof, no need for thermostat guards

Freeze protection...prevents costly freeze damage

EEPROM memory...no loss of program

6 hour reserve time for clock...no need to reprogram day or time after

power outage

Auxiliary output...can be used for lighting and/or economizer override

Discharge air sensor...can be used to monitor unit efficiency

Low/High balance point...protect and optimize system performance

3 Heat/2 Cool...support single and two stages heat pump with one auxiliary

heat stage