VEGA KFD0-SCS-Ex1.55 User Manual

Kfd0-scs-ex1.55 smart repeaters, Composition

Advertising
background image

1

122

60

9_

EN

G.xm

l

2

003

-03-

2

5

Subject to reasonable modifications due to technical advances.

Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com

KFD0-SCS-Ex1.55

SMART repeaters

Field circuit EEx ib IIC

Transmitter
Positioner
I/P converter

Current source
4 mA ... 20 mA

or

Voltage supply

Saf

e area

Hazar

dous area

Measuring resistors

Supply circuit

SMART

communicator

SMART

communicator

2-

U/I

1+

2-

2-

3-

2-

1+

2-

1+

8-

8-

9+

9+

8-

9+

8-

9+

50 mA

33 V

I

?

Composition

Transmission range 4 mA ... 20 mA
• 1-channel

• Field circuit EEx ib IIC

• Loop powered

• Lead monitoring

• Conductive for HART communication

(galvanically isolated)

• Universal application for transmitters,

position controllers and I/P
converters

• Only 5 V voltage drop

• Test sockets for HART

• EMC acc. to NAMUR NE 21

The universal module
KFD0-SCS-Ex1.55 does not require
auxiliary power for the isolation of
4 mA ... 20 mA current loops. It is
therefore, low in cost and has a
noticeably low power loss as compared
to active isolator modules. The module
isolates 4 mA ... 20 mA signals from
transmitters and positioners and is
therefore, bidirectionally HART
compatible. The HART transmitters and
HART positioners may thus, be
configured in the safe area as well as
the hazardous area. The low 5 V
voltage drop also allows for transmitter-
applications with unstable power
sources in the range of
20 V DC ... 30 V DC.
In addition, the voltage drop across the
resistance (load) of the active
measurement input must be considered
when calculating the field voltage
(terminals 1+ and 2-).
Lead breakage monitoring is possible
by means of the reaction of the field
current signal to the safe area, which
means the control system must monitor
whether the 4 mA ... 20 mA range was
exceeded or fallen short of.
The module may also be used for
controlling Ex-i valves, light signals, etc.
based on the internal voltage limits
(safe area). Terminals 8- and 9+ in this
case are driven with a 24 V binary
signal.

Function